Rockwell Automation 20B PowerFlex 700 AC Drives Vector Control (v4.001 and up) User Manual
Page 46

46
Rockwell Automation Publication 20B-UM002G-EN-P - July 2014
Chapter 1
Programming and Parameters
UTILIT
Y
Dr
iv
e M
em
or
y
201 [Language]
Selects the display language when using an LCD
HIM. This parameter is not functional with an
LED HIM.
Options 6, 8 and 9 are “Reserved.”
This parameter is not reset when “Reset to
Defaults” is selected.
Default:
Options:
0
0
1
2
3
4
5
7
10
“Not Selected”
“Not Selected”
“English”
“Francais”
“Español”
“Italiano”
“Deutsch”
“Português”
“Nederlands”
202 [Voltage Class]
Configures the drive current rating and associates
it with the selected voltage (i.e. 400 or 480V).
Normally used when downloading parameter
sets. Min/Max & Default values will be changed
for parameters; 41-47, 54, 55, 62, 63, 69, 70-72,
82, 148, 158.
This parameter is not reset when “Reset to
Defaults” is selected.
Important: Frames 5…10 - If changing voltage
class, verify correct voltage on the fan
transformer. See “Selecting /Verifying Fan
Voltage” in the Installation Instructions,
publicatio
Default:
Options:
2
3
4
5
Based on Drive Cat. No.
“Low Voltage”
“High Voltage”
“Reserved”
“Reserved”
…
…
203 [Drive Checksum]
Provides a checksum value that indicates
whether or not a change in drive programming
has occurred.
Default:
Min/Max:
Units:
Read Only
0/65535
1
204 [Dyn UsrSet Cnfg]
Enables/Disables dynamic selection of user parameter sets.
Important: In dynamic mode, changes to the parameters are not saved to nonvolatile storage.
Switching user sets restores the values last saved before enabling dynamic mode.
205 [Dyn UsrSet Sel]
Selects user set if [Dyn UsrSet Cnfg] = xxxx xx11.
Important: All digital input selections (parameters 361-366) must be identical in all three user
sets for proper Dynamic User Set operation (even if only two sets are used).
206 [Dyn UserSet Actv]
Indicates the active user set and if the operation is dynamic or
normal.
Read Only
Fil
e
Gr
oup
No
.
Parameter Name & Description
See
page 16
for symbol descriptions
Values
Rela
ted
0
x
x
0
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
Bit #
Factory Default Bit Values
Dynamic Mode
Ctrl S
our
ce
Dynamic Mode
1 = Enabled
0 = Disabled
Ctrl Source
1 = [Dyn UserSet Sel]
0 = Digital Inputs
x = Reserved
0
x
x
0
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 = Enabled
0 = Disabled
x = Reserved
Bit #
Factory Default Bit Values
UserS
et S
el1
UserS
et S
el2
0
1
0
1
User Set 1
User Set 2
User Set 3
User Set 3
0
0
1
1
0
0
0
0
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 = Condition True
0 = Condition False
x = Reserved
Bit #
Dynamic Mode
User S
et 1
User S
et 2
User S
et 3