Monitor file – Rockwell Automation 20B PowerFlex 700 AC Drives Vector Control (v4.001 and up) User Manual
Page 21

Rockwell Automation Publication 20B-UM002G-EN-P - July 2014
21
Programming and Parameters
Chapter 1
Monitor File
Fi
le
Grou
p
No
.
Parameter Name & Description
See
for symbol descriptions
Values
Re
la
te
d
MON
IT
O
R
Meter
in
g
001 [Output Freq]
Output frequency present at T1, T2 & T3 (U, V &
W)
Default:
Min/Max:
Units:
Read Only
–/+[Maximum Freq]
0.1 Hz
002 [Commanded Speed]
Value of the active Speed/Frequency Reference.
Displayed in Hz or RPM, depending on value of
[Speed Units].
Default:
Min/Max:
Units:
Read Only
–/+[Maximum Speed]
0.1 Hz
0.1 RPM
003 [Output Current]
The total output current present at T1, T2 & T3 (U,
V & W).
Default:
Min/Max:
Units:
Read Only
0.0/Drive Rated Amps x 2
0.1 Amps
004 [Torque Current]
Based on the motor, the amount of current that is
in phase with the fundamental voltage
component.
Default:
Min/Max:
Units:
Read Only
Drive Rating x –2/+2
0.1 Amps
005 [Flux Current]
Amount of current that is out of phase with the
fundamental voltage component.
Default:
Min/Max:
Units:
Read Only
Drive Rating x –2/+2
0.1 Amps
006 [Output Voltage]
Output voltage present at terminals T1, T2 & T3
(U, V & W).
Default:
Min/Max:
Units:
Read Only
0.0/Drive Rated Volts
0.1 VAC
007 [Output Power]
Output power present at T1, T2 & T3
(U, V & W).
[Output Power] = SQRT (3) x [Output Voltage] x
[Output Current] x [Output Powr Fctr]
Default:
Min/Max:
Units:
Read Only
0.0/Drive Rated kW x 2
0.1 kW
008 [Output Powr Fctr]
Output Power Factor =
ABS (SIN (Commanded Voltage Vector Angle -
Measured Current Vector Angle))
Default:
Min/Max:
Units:
Read Only
0.00/1.00
0.01
009 [Elapsed MWh]
Accumulated output energy of the drive.
Default:
Min/Max:
Units:
Read Only
0.0/214748352.0 MWh
0.1 MWh
010 [Elapsed Run Time]
Accumulated time drive is outputting power.
Default:
Min/Max:
Units:
Read Only
0.0/214748352.0 Hrs
0.1 Hrs
011 [MOP Reference]
Value of the signal at MOP (Motor Operated
Potentiometer).
Default:
Min/Max:
Units:
Read Only
–/+[Maximum Speed]
0.1 Hz
0.1 RPM
012 [DC Bus Voltage]
Present DC bus voltage level.
Default:
Min/Max:
Units:
Read Only
0.0/Based on Drive Rating
0.1 VDC
013 [DC Bus Memory]
6 minute average of DC bus voltage level.
Default:
Min/Max:
Units:
Read Only
0.0/Based on Drive Rating
0.1 VDC
014 [Elapsed kWh]
Accumulated output energy of the drive.
Default:
Min/Max:
Units:
Read Only
0.0/429496729.5 kWh
0.1 kWh
016
017
[Analog In1 Value]
[Analog In2 Value]
Value of the signal at the analog inputs.
Default:
Min/Max:
Units:
Read Only
0.000/20.000 mA
–/+10.000V
0.001 mA
0.001 Volt