It is possible to use the Assisted Start Up to tune the motor. However, it is
recommended that the motor be disconnected from the hoist/crane equipment
during the routine. If this is not possible, refer to steps
through
on the
following pages.
Initial Static Auto Tune Test
1. Set the following parameters as shown.
2. Press the Start key on the HIM. Parameters 062-064 will be updated.
Motor Rotation/Encoder Direction Test
3. Set the following parameters as shown.
ATTENTION: To guard against personal injury and/or equipment damage
caused by unexpected brake release, verify the Digital Out 1 brake connections
and/or programming. The default drive configuration energizes the Digital Out
1 relay when power is applied to the drive. The PowerFlex 700 drive will not
control the mechanical brake until TorqProve is enabled. If the brake is
connected to this relay, it could be released. If necessary, disconnect the relay
output until wiring/programming can be completed and verified.
No.
Name
Value
Notes
380
[Digital Out1 Sel]
“9, At Speed”
keeps brake engaged during test
041-045
[Motor NP . . .]
per nameplate
enter motor nameplate data
053
[Motor Cntl Sel]
“4, FVC Vector”
080
[Feedback Select]
“3, Encoder”
061
[Autotune]
“1, Static Tune”
No.
Name
Value
Notes
053
[Motor Cntl Sel]
“0, Sensrls Vect”
080
[Feedback Select]
“0, Open Loop”
090
[Speed Ref A Sel]
“11, Preset Spd1”
238
[Fault Config 1]
Bit 8, “In PhaseLoss” = 1
Bit 12, “OutPhaseLoss” = 1
380
[Digital Out1 Sel]
“4, Run”
releases brake
IMPORTANT
If the direction of travel is critical at this point, perform short jogs to
determine which run direction (RUNFWD or RUNREV) should be used
in the next steps.