Entering a condition string, Figure 4-10 select output screen -28, Figure 4-11 program output screen -28 – INFICON MDC-260 Thin Film Deposition Controller User Manual
Page 64

MDC-260 DEPOSITION CONTROLLER
PROGRAMMING AND CONTROLLER SETUP
4-28
Selecting Program Outputs from the System Setup menu will present the Select
Output screen.
Figure 4-10 Select Output Screen
Selecting an output with the Right-arrow or Enter key will present the screen
which permits definition of the output, as shown below.
The Left-arrow, Right-arrow, Up-arrow and Down-arrow keys provide access to
the Output Name, card#, pin# and Condition string edit fields. A 16-digit name
can be assigned to the logical input. Any entry other than 1 or 2 will be ignored
for the card#, as will a pin# less than 2 or greater than 9.
Figure 4-11 Program Output Screen
The output condition string is a logical statement that determines the state of the
output. The output relay is closed when the condition string is evaluated as true.
Otherwise, the relay is open. Each output condition string is evaluated ten times
per second (every 100 milliseconds).
4.3.3.3.1 ENTERING A CONDITION STRING
A condition string comprises one or more individual conditions linked together by
the logical operators ! NOT, & AND, | OR and parentheses ( ). Conditions are
chosen from a list. To enter a condition string correctly you must follow these
rules:
There must be an equal number of closed and open parentheses.
All conditions must be separated by either the & or the | operator.
Condition strings cannot end in an operator.
To enter a condition string, first highlight the condition string field. The second
line from the bottom of the screen displays the valid operators and parentheses.
Select Output
01
End of Process
-
02 Wire feed Al
03 Layer Complete
04 Procs Complete
05
06
07
- View/Edit 08
↓
Pin#-Return
Output Name
Wire Feed Al
------- 2 21
Conditions Al & FeedHold
Valid operators: 1=!, 2=(
0=Add condition, to save