To define a custom (Private) Alarm template, or modify existing
Alarm Template settings, complete the fields in the General
Parameters, Notifications, and Comments tabs.
Note: You require Manage Alarm Templates Right to modify
existing Alarm Templates. For more information, see
“Alarm Templates” on page 52.
6
When you finish creating your Threshold template, click
Options |
Save
.
To apply the Threshold template to a Location, see “Setting Up
Location Thresholds” on page 78.
Multi-threshold Template
A multi-threshold template can have up to five threshold settings.
To create a multi-threshold template:
1
From the viewLinc desktop, select Options | System Con-
figuration | Templates |
Threshold Templates
.
2
In the Threshold Templates window, click
Options
|
Add
Multi-Threshold Template
.
3
Double-click anywhere in the title to change it.
4
Set the Threshold conditions:
•
Units
: Select the Channel’s measurement units.
•
Deadband
: Specify the measurement range you want
viewLinc to ignore (this range accommodates minor fluc-
tuations which you do not want to trigger an alarm).
•
Type
: Identify the threshold as a High limit (High or
HighHigh), or Low limit (Low or LowLow), or, indicate
the rate of change in units (ROC Units).
•
Value:
Enter the threshold limit.