Common values for both TCP and COM port connections:
sample_rate = 10s, 90s (default), 12m, 2h, 12h, 2d,
or 12d
•
Optional values for COM port connection:
baud = 300, 2400, 4800, 9600, 19200 (default), 57600,
or 115200
stopbits = 1(default) or 2
databits = 7 or 8(default)
parity = odd, even or none(default)
•
To set HMT140:
hmt140 serial_number
Q:
How do you add IP addresses for Vaisala Veriteq Devices
using Digi or vNet Devices?
A:
You don't. However you do assign IP addresses to your
communication Devices, Vaisala Veriteq Devices. Because viewLinc
communicates using COM ports, attaching Vaisala Veriteq Devices to the
network using Ethernet/IP addresses requires the use of a networking
Device, vNet or Digi Devices.
vNet or Digi Devices create virtual COM ports that allow Vaisala Veriteq
Devices to communicate with viewLinc using Ethernet.
We recommend that you do not use dynamic IP address for your
Devices; instead, use a reserved or static IP address (obtained from your
IT department). IP addresses are assigned to vNet or Digi Devices during
driver configuration. Refer to the Vaisala Veriteq Quick Start Guide for
vNet or Digi Devices for installation instructions.
•
For more about vNet Devices, see
http://www.vaisala.com/en/lifescience.
•
For more about Digis, see www.digi.com.
Q:
How can I connect via wireless or ethernet with 300
series Devices?
A:
Internal LAN-1 Module (Ethernet): Allows single PTU300*,
HMT330, DMT340 or MMT330 transmitter to connect to the viewLinc