Watlow EZ-ZONE

®

RMH Module

92

Chapter 4 Setup Page

RM High Density Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[`FiL]
[ FiL]

Math (1 to 24)

Filter

Filtering smooths out the

output signal of this func-

tion block. Increase the

time to increase filtering.

0.0 to 60.0 seconds

0.0

6594

[offset 70]

0x7D

(125)

1 to 24

0x1C (28)

- - - -

25028

float

RWES

[`uAr]
[`Set]
Variable Menu

[tyPE]
[tyPE]

Variable (1 to 24)

Data Type

Set the variable's data

type.

[AnLg]

Analog (1215)

[`Dig]

Digital (1220)

Analog

16060

[offset 20]

0x66 (102)

1 to 24

1

152

2001

uint
RWES

[Unit]
[Unit]

Variable (1 to 24)

Units

Set the variable's units.

[`A;tp]

Absolute Temperature

(1540)

[`r;tp]

Relative Temperature

(1541)

[PWr]

Power (73)

[`Pro]

Process (75)

[``rh]

Relative Humidity

(1538)

[nonE]

None (61)

Absolute

Temper-

ature

16072

[offset 20]

0x66 (102)

1 to 24

7

- - - -

2007

uint
RWES

[`Dig]
[ dig]

Variable (1 to 24)

Digital

Set the variable's value.

[`oFF]

Off (62)

[``on]

On (63)

Off

16062

[offset 20]

0x66 (102)

1 to 24

2

153

2002

uint
RWES

[anLg]
[AnLg]

Variable (1 to 24)

Analog

Set the variable's value.

-1,999.000 to 9,999.000

Note:

Stored in °F only

0.0

16064

[offset 20]

0x66 (102)

1 to 24

3

212

2003

float
RWES

No Dis-

play

Variable (1 to 24)

Output Value

Off (62)
On (63)
-1,999.000 to 9,999.000

- - - -

16066

[offset 20]

0x66 (102)

1 to 24

4

- - - -

2004

float
R

[gLbL]
[`Set]
Global Menu

[`C_F]
[ C_F]

Global

Display Units

Select which scale to use

for temperature.

[```F]

°F (30)

[```C]

°C (15)

°F

368

0x67 (103)

1

5

85

3005

uint

RWES

[AC;LF]
[AC.LF]

Global

AC Line Frequency

Set the frequency to the ap-

plied ac line power source.

[``50]

50 Hz (3)

[``60]

60 Hz (4)

60 Hz

- - - -

0x65 (101)

1

0x22 (34)

- - - -

1034

uint

RWES

[d;prs]
[dPrS]

Global

Display Pairs

Defines the number of

display pairs at the home

page of an RUI

1 to 25

2

- - - -

0x67 (103)

1

0x1C (28)

- - - -

3028

uint

RWES

Note:

Some values will be rounded off to fit in the four-character display.

Full values can be read with other interfaces.

Note:

If there is only one instance of a menu, no submenus will appear.

** These parameters/prompts are available in these menus with firmware revisions 6.0 and

above.

R: Read

W: Write

E:

EEPROM

S:

User

Set