Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[`FiL]
[ FiL]
Math (1 to 24)
Filter
Filtering smooths out the
output signal of this func-
tion block. Increase the
time to increase filtering.
0.0 to 60.0 seconds
0.0
6594
[offset 70]
0x7D
(125)
1 to 24
0x1C (28)
- - - -
25028
float
RWES
[`uAr]
[`Set]
Variable Menu
[tyPE]
[tyPE]
Variable (1 to 24)
Data Type
Set the variable's data
type.
[AnLg]
Analog (1215)
[`Dig]
Digital (1220)
Analog
16060
[offset 20]
0x66 (102)
1 to 24
1
152
2001
uint
RWES
[Unit]
[Unit]
Variable (1 to 24)
Units
Set the variable's units.
[`A;tp]
Absolute Temperature
(1540)
[`r;tp]
Relative Temperature
(1541)
[PWr]
Power (73)
[`Pro]
Process (75)
[``rh]
Relative Humidity
(1538)
[nonE]
None (61)
Absolute
Temper-
ature
16072
[offset 20]
0x66 (102)
1 to 24
7
- - - -
2007
uint
RWES
[`Dig]
[ dig]
Variable (1 to 24)
Digital
Set the variable's value.
[`oFF]
Off (62)
[``on]
On (63)
Off
16062
[offset 20]
0x66 (102)
1 to 24
2
153
2002
uint
RWES
[anLg]
[AnLg]
Variable (1 to 24)
Analog
Set the variable's value.
-1,999.000 to 9,999.000
Note:
Stored in °F only
0.0
16064
[offset 20]
0x66 (102)
1 to 24
3
212
2003
float
RWES
No Dis-
play
Variable (1 to 24)
Output Value
Off (62)
On (63)
-1,999.000 to 9,999.000
- - - -
16066
[offset 20]
0x66 (102)
1 to 24
4
- - - -
2004
float
R
[gLbL]
[`Set]
Global Menu
[`C_F]
[ C_F]
Global
Display Units
Select which scale to use
for temperature.
[```F]
°F (30)
[```C]
°C (15)
°F
368
0x67 (103)
1
5
85
3005
uint
RWES
[AC;LF]
[AC.LF]
Global
AC Line Frequency
Set the frequency to the ap-
plied ac line power source.
[``50]
50 Hz (3)
[``60]
60 Hz (4)
60 Hz
- - - -
0x65 (101)
1
0x22 (34)
- - - -
1034
uint
RWES
[d;prs]
[dPrS]
Global
Display Pairs
Defines the number of
display pairs at the home
page of an RUI
1 to 25
2
- - - -
0x67 (103)
1
0x1C (28)
- - - -
3028
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E:
EEPROM
S: