Watlow EZ-ZONE

®

RMH Module

62

Chapter 4 Setup Page

RM High Density Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[`r;En]
[ r.En]

Control Loop (1 to 16)

Remote Enable

Enable this loop to switch

control to the remote set

point.

[``no]

No (59)

[`YES]

Yes (106)

No

5260
[offset 80]

0x6B

(107)

1 to 16

0x15 (21)

38

7021

uint

RWES

[SFn;b]
[SFn.b]

Control Loop (1 to 16)

Source Function B

Set the type of function

that will be used for this

source.

[none]

None (61)

[``Ai]

Analog Input (142)

[Curr]

Current (22)

[`C;pr]

Cool Power (161)

[`h;pr]

Heat Power (160)

[pwr]

Power (73)

[`lnr]

Linearization (238)

[mat]

Math (240)

[``Pu]

Process Value (241)

[`sp;C]

Set Point Closed (242)

[`sp;o]

Set Point Open (243)

[`uar]

Variable (245)

None

5264

[offset 80]

0x6B

(107)

1 to 16

0x17 (23)

- - - -

7023

uint
RWES

[`si;b]
[ Si.b]

Control Loop (1 to 16)

Source Instance B

Select the instance of the

function selected above.

1 to 250

1

5266

[offset 80]

0x6B

(107)

1 to 16

0x18 (24)

- - - -

7024

uint

RWES

[`S2;b]
[ SZ.b]

Control Loop (1 to 16)

Source Zone B

Set the zone of the function

selected above.

0 to 16

0

5270
[offset 80]

0x6B

(107)

1 to 16

0x1A (26)

- - - -

7026

uint
RWES

[`r;ty]
[ r.ty]

Control Loop (1 to 16)

Remote Set Point Type

Enable this loop to switch

control to the remote set

point.

[auto]

Auto (10)

[man]

Manual (54)

Auto

5262
[offset 80]

0x6B

(107)

1 to 16

0x16 (22)

- - - -

7022

uint

RWES

[`UFA]
[UFA]

Control Loop (1 to 16)

User Failure Action

Select what the controller

outputs will do when the

user switches control to

manual mode.

[`oFF]

Off, sets output power

to 0% (62)

[bPLS]

Bumpless transfer

maintains same output

power, if it was less than

75% and stable, otherwise

0% (14)

[MAn]

Manual power, sets

output power to Manual

Power setting (33)

[USEr]

User, sets output

power to last open-loop set

point the user entered (100)

User

5242
[offset 80]

0x6B

(107)

1 to 16

0xC (12)

- - - -

7012

uint

RWES

Note:

Some values will be rounded off to fit in the four-character display.

Full values can be read with other interfaces.

Note:

If there is only one instance of a menu, no submenus will appear.

** These parameters/prompts are available in these menus with firmware revisions 6.0 and

above.

R: Read

W: Write

E:

EEPROM

S:

User

Set