Watlow EZ-ZONE RMH User Manual
Page 65

Watlow EZ-ZONE
®
RMH Module
•
62
•
Chapter 4 Setup Page
RM High Density Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[`r;En]
[ r.En]
Control Loop (1 to 16)
Remote Enable
Enable this loop to switch
control to the remote set
point.
[``no]
No (59)
[`YES]
Yes (106)
No
5260
[offset 80]
0x6B
(107)
1 to 16
0x15 (21)
38
7021
uint
RWES
[SFn;b]
[SFn.b]
Control Loop (1 to 16)
Source Function B
Set the type of function
that will be used for this
source.
[none]
None (61)
[``Ai]
Analog Input (142)
[Curr]
Current (22)
[`C;pr]
Cool Power (161)
[`h;pr]
Heat Power (160)
[pwr]
Power (73)
[`lnr]
Linearization (238)
[mat]
Math (240)
[``Pu]
Process Value (241)
[`sp;C]
Set Point Closed (242)
[`sp;o]
Set Point Open (243)
[`uar]
Variable (245)
None
5264
[offset 80]
0x6B
(107)
1 to 16
0x17 (23)
- - - -
7023
uint
RWES
[`si;b]
[ Si.b]
Control Loop (1 to 16)
Source Instance B
Select the instance of the
function selected above.
1 to 250
1
5266
[offset 80]
0x6B
(107)
1 to 16
0x18 (24)
- - - -
7024
uint
RWES
[`S2;b]
[ SZ.b]
Control Loop (1 to 16)
Source Zone B
Set the zone of the function
selected above.
0 to 16
0
5270
[offset 80]
0x6B
(107)
1 to 16
0x1A (26)
- - - -
7026
uint
RWES
[`r;ty]
[ r.ty]
Control Loop (1 to 16)
Remote Set Point Type
Enable this loop to switch
control to the remote set
point.
[auto]
Auto (10)
[man]
Manual (54)
Auto
5262
[offset 80]
0x6B
(107)
1 to 16
0x16 (22)
- - - -
7022
uint
RWES
[`UFA]
[UFA]
Control Loop (1 to 16)
User Failure Action
Select what the controller
outputs will do when the
user switches control to
manual mode.
[`oFF]
Off, sets output power
to 0% (62)
[bPLS]
Bumpless transfer
maintains same output
power, if it was less than
75% and stable, otherwise
0% (14)
[MAn]
Manual power, sets
output power to Manual
Power setting (33)
[USEr]
User, sets output
power to last open-loop set
point the user entered (100)
User
5242
[offset 80]
0x6B
(107)
1 to 16
0xC (12)
- - - -
7012
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E:
EEPROM
S:
User
Set