Watlow EZ-ZONE RMH User Manual
Page 58
Watlow EZ-ZONE
®
RMH Module
•
55
•
Chapter 4 Setup Page
RM High Density Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[SFn;E]
[SFn.E]
Process Value (1 to 16)
Source Function E
Set the type of function
that will be used for this
source.
[nonE]
None (61)
[ALM]
Alarm (6)
[`CPE]
Compare (230)
[`Ctr]
Counter (231)
[`dio]
Digital I/O (1142)
[Ent;A]
Profile Event Out A
(233)
[Ent;b]
Profile Event Out B
(234)
[Ent;C]
Profile Event Out C
(235)
[Ent;d]
Profile Event Out D
(236)
[Ent;E]
Profile Event Out E
(247)
[Ent;F]
Profile Event Out F
(248)
[Ent;g]
Profile Event Out G
(249)
[Ent;h]
Profile Event Out H
(250)
[`FUn]
Function Key (1001)
[`lgC]
Logic (239)
[tMr]
Timer (244)
[`uAr]
Variable (245)
None
8228
[offset 70]
0x7E
(126)
1 to 16
5
- - - -
26005
uint
RWES
[`Si;E]
[ Si.E]
Process Value (1 to 16)
Source Instance E
Set the instance of the
function selected above.
1 to 250
1
8238
[offset 70]
0x7E
(126)
1 to 16
0x0A (10)
- - - -
26010
uint
RWES
[`s2;E]
[ SZ.E]
Process Value (1 to 16)
Source Zone E
Set the zone of the function
selected above.
0 to 16
0
8248
[offset 70]
0x7E
(126)
1 to 16
0x0F (15)
- - - -
26015
uint
RWES
[``C;p]
[ SZ.E]
Process Value (1 to 16)
Cross Over Point
Enter a value where the
Output Value switches
from Source A to Source
B value. This applies only
when the Process function
is set to Cross Over.
-1,999.000 to 9,999.000 units
or °F
-1,128.333 to 5,537.223 °C
100.0
8266
[offset 70]
0x7E
(126)
1 to 16
0x18 (24)
- - - -
26024
float
RWES
[``C;b]
[ SZ.E]
Process Value (1 to 16)
Cross Over Band
Enter a band centered
about the Cross Over
Point where Output Value
switches from Source A to
Source B Value. This ap-
plies only when the Process
function is set to Cross
Over.
-1,999.000 to 9,999.000 units
or °F
-1,128.333 to 5,537.223 °C
10.0
8268
[offset 70]
0x7E
(126)
1 to 16
0x19 (25)
- - - -
26025
float
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E:
EEPROM
S:
User
Set