Watlow EZ-ZONE

®

RMH Module

55

Chapter 4 Setup Page

RM High Density Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[SFn;E]
[SFn.E]

Process Value (1 to 16)

Source Function E

Set the type of function

that will be used for this

source.

[nonE]

None (61)

[ALM]

Alarm (6)

[`CPE]

Compare (230)

[`Ctr]

Counter (231)

[`dio]

Digital I/O (1142)

[Ent;A]

Profile Event Out A

(233)

[Ent;b]

Profile Event Out B

(234)

[Ent;C]

Profile Event Out C

(235)

[Ent;d]

Profile Event Out D

(236)

[Ent;E]

Profile Event Out E

(247)

[Ent;F]

Profile Event Out F

(248)

[Ent;g]

Profile Event Out G

(249)

[Ent;h]

Profile Event Out H

(250)

[`FUn]

Function Key (1001)

[`lgC]

Logic (239)

[tMr]

Timer (244)

[`uAr]

Variable (245)

None

8228

[offset 70]

0x7E

(126)

1 to 16

5

- - - -

26005

uint
RWES

[`Si;E]
[ Si.E]

Process Value (1 to 16)

Source Instance E

Set the instance of the

function selected above.

1 to 250

1

8238

[offset 70]

0x7E

(126)

1 to 16

0x0A (10)

- - - -

26010

uint
RWES

[`s2;E]
[ SZ.E]

Process Value (1 to 16)

Source Zone E

Set the zone of the function

selected above.

0 to 16

0

8248

[offset 70]

0x7E

(126)

1 to 16

0x0F (15)

- - - -

26015

uint
RWES

[``C;p]
[ SZ.E]

Process Value (1 to 16)

Cross Over Point

Enter a value where the

Output Value switches

from Source A to Source

B value. This applies only

when the Process function

is set to Cross Over.

-1,999.000 to 9,999.000 units

or °F

-1,128.333 to 5,537.223 °C

100.0

8266

[offset 70]

0x7E

(126)

1 to 16

0x18 (24)

- - - -

26024

float
RWES

[``C;b]
[ SZ.E]

Process Value (1 to 16)

Cross Over Band

Enter a band centered

about the Cross Over

Point where Output Value

switches from Source A to

Source B Value. This ap-

plies only when the Process

function is set to Cross

Over.

-1,999.000 to 9,999.000 units

or °F

-1,128.333 to 5,537.223 °C

10.0

8268

[offset 70]

0x7E

(126)

1 to 16

0x19 (25)

- - - -

26025

float
RWES

Note:

Some values will be rounded off to fit in the four-character display.

Full values can be read with other interfaces.

Note:

If there is only one instance of a menu, no submenus will appear.

** These parameters/prompts are available in these menus with firmware revisions 6.0 and

above.

R: Read

W: Write

E:

EEPROM

S:

User

Set