beautypg.com

Watlow EZ-ZONE RMH User Manual

Page 94

background image

Watlow EZ-ZONE

®

RMH Module

91

Chapter 4 Setup Page

RM High Density Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[`Si;E]
[ Si.E]

Math (1 to 24)

Source Instance E

Set the instance of the

function selected above.

1 to 250

1

6558

[offset 70]

0x7D

(125)

1 to 24

0xA (10)

- - - -

25010

uint
RWES

[`s2;E]
[ SZ.E]

Math (1 to 24)

Source Zone E

Set the zone of the function

selected above.

0 to 16

0

6568

[offset 70]

0x7D

(125)

1 to 24

0xF (15)

- - - -

25015

uint
RWES

[`S;Lo]
[ S.Lo]

Math (1 to16)

Input Scale Low

Active for Process or Devia-

tion Scale of Source A only.

-1,999.000 to 9,999.000 °F

or units

-1,128.333 to 5537.223 °C

0.0

6586

[offset 70]

0x7D

(125)

1 to 24

0x18 (24)

104

25024

float

RWES

[`S;hi]
[ S.hi]

Math (1 to 24)

Input Scale High

Active for Process or Devia-

tion Scale of Source A only

-1,999.000 to 9,999.000 °F

or units

-1,128.333 to 5537.223 °C

1.0

6588

[offset 70]

0x7D

(125)

1 to 24

0x19 (25)

105

25025

float

RWES

[Unit]
[Unit]

Math (1 to 24)

Units

Set the units of Source A.

[`Src]

Source (1539)

[nonE]

None (61)

[`A;tP]

Absolute Temperature

(1540)

[`r;tp]

Relative Tempera-

ture (1541)

[PWr]

Power (73)

[`pro]

Process (75)

[``rh]

Relative Humidty

(1538)

Source

6602

[offset 70]

0x7D

(125)

1 to 24

0x20 (32)

- - - -

25032

uint
RWES

[`r;Lo]
[ r.Lo]

Math (1 to 24)

Output Range Low

Active for Process or Devia-

tion Scale of Source A only.

-1,999.000 to 9,999.000 °F

or units

-1,128.333 to 5537.223 °C

0.0

6590

[offset 70]

0x7D

(125)

1 to 24

0x1A (26)

106

25026

float

RWES

[`r;hi]
[ r.hi]

Math (1 to 24)

Output Range High

Active for Process or Devia-

tion Scale of Source A only

-1,999.000 to 9,999.000 °F

or units

-1,128.333 to 5537.223 °C

1.0

6592

[offset 70]

0x7D

(125)

1 to 24

0x1B (27)

107

25027

float

RWES

[p;unt]
[P.unt]

Math (1 to 24)

Pressure Units

Select units of Source A

when function is Pressure

to Altitude conversion only

[`psi]

Pounds per square

inch (1671)

[mbr]

mbar (1672)

[torr]

Torr (1673)

[pasc]

Pascal (1674)

[atm]

Atmosphere (1675)

Pressure

Units

6598

[offset 70]

0x7D

(125)

1 to 24

0x1E (30)

- - - -

25030

uint

RWES

[a;unt]
[A.unt]

Math (1 to 24)

Altitude Units

Select units of output value

when function is Pressure

to Altitude conversion only.

[``ft]

Feet (1674)

[`Hft]

Kilofeet (1671)

Kilofeet

6600

[offset 70]

0x7D

(125)

1 to 24

0x1F (31)

- - - -

25031

uint

RWES

Note:

Some values will be rounded off to fit in the four-character display.

Full values can be read with other interfaces.

Note:

If there is only one instance of a menu, no submenus will appear.

** These parameters/prompts are available in these menus with firmware revisions 6.0 and

above.

R: Read

W: Write

E:

EEPROM

S:

User

Set