Watlow EZ-ZONE RMH User Manual
Page 94

Watlow EZ-ZONE
®
RMH Module
•
91
•
Chapter 4 Setup Page
RM High Density Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[`Si;E]
[ Si.E]
Math (1 to 24)
Source Instance E
Set the instance of the
function selected above.
1 to 250
1
6558
[offset 70]
0x7D
(125)
1 to 24
0xA (10)
- - - -
25010
uint
RWES
[`s2;E]
[ SZ.E]
Math (1 to 24)
Source Zone E
Set the zone of the function
selected above.
0 to 16
0
6568
[offset 70]
0x7D
(125)
1 to 24
0xF (15)
- - - -
25015
uint
RWES
[`S;Lo]
[ S.Lo]
Math (1 to16)
Input Scale Low
Active for Process or Devia-
tion Scale of Source A only.
-1,999.000 to 9,999.000 °F
or units
-1,128.333 to 5537.223 °C
0.0
6586
[offset 70]
0x7D
(125)
1 to 24
0x18 (24)
104
25024
float
RWES
[`S;hi]
[ S.hi]
Math (1 to 24)
Input Scale High
Active for Process or Devia-
tion Scale of Source A only
-1,999.000 to 9,999.000 °F
or units
-1,128.333 to 5537.223 °C
1.0
6588
[offset 70]
0x7D
(125)
1 to 24
0x19 (25)
105
25025
float
RWES
[Unit]
[Unit]
Math (1 to 24)
Units
Set the units of Source A.
[`Src]
Source (1539)
[nonE]
None (61)
[`A;tP]
Absolute Temperature
(1540)
[`r;tp]
Relative Tempera-
ture (1541)
[PWr]
Power (73)
[`pro]
Process (75)
[``rh]
Relative Humidty
(1538)
Source
6602
[offset 70]
0x7D
(125)
1 to 24
0x20 (32)
- - - -
25032
uint
RWES
[`r;Lo]
[ r.Lo]
Math (1 to 24)
Output Range Low
Active for Process or Devia-
tion Scale of Source A only.
-1,999.000 to 9,999.000 °F
or units
-1,128.333 to 5537.223 °C
0.0
6590
[offset 70]
0x7D
(125)
1 to 24
0x1A (26)
106
25026
float
RWES
[`r;hi]
[ r.hi]
Math (1 to 24)
Output Range High
Active for Process or Devia-
tion Scale of Source A only
-1,999.000 to 9,999.000 °F
or units
-1,128.333 to 5537.223 °C
1.0
6592
[offset 70]
0x7D
(125)
1 to 24
0x1B (27)
107
25027
float
RWES
[p;unt]
[P.unt]
Math (1 to 24)
Pressure Units
Select units of Source A
when function is Pressure
to Altitude conversion only
[`psi]
Pounds per square
inch (1671)
[mbr]
mbar (1672)
[torr]
Torr (1673)
[pasc]
Pascal (1674)
[atm]
Atmosphere (1675)
Pressure
Units
6598
[offset 70]
0x7D
(125)
1 to 24
0x1E (30)
- - - -
25030
uint
RWES
[a;unt]
[A.unt]
Math (1 to 24)
Altitude Units
Select units of output value
when function is Pressure
to Altitude conversion only.
[``ft]
Feet (1674)
[`Hft]
Kilofeet (1671)
Kilofeet
6600
[offset 70]
0x7D
(125)
1 to 24
0x1F (31)
- - - -
25031
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E:
EEPROM
S:
User
Set