Watlow EZ-ZONE

®

RMH Module

59

Chapter 4 Setup Page

RM High Density Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[SFn;A]
[SFn.A]

Action (1 to 24)

Source Function A

Set the event or function

that will trigger the action.

[nonE]

None (61)

[ALM]

Alarm (6)

[`CPE]

Compare (230)

[`Ctr]

Counter (231)

[`dio]

Digital I/O (1142)

[Ent;A]

Profile Event Out A

(233)

[Ent;b]

Profile Event Out B

(234)

[Ent;C]

Profile Event Out C

(235)

[Ent;d]

Profile Event Out D

(236)

[Ent;E]

Profile Event Out E

(247)

[Ent;F]

Profile Event Out F

(248)

[Ent;g]

Profile Event Out G

(249)

[Ent;h]

Profile Event Out H

(250)

[`FUn]

Function Key (1001)

[LiM]

Limit (126)

[`LgC]

Logic (239)

[tMr]

Timer (244)

[`uAr]

Variable (245)

None

2190
[offset 20]

0x6E

(110)

1 to 24

6

- - - -

10006

uint
RWES

[`Si;A]
[ Si.A]

Action (1 to 24)

Source Instance A

Set the instance of the

function selected above.

1 to 250

1

2182
[offset 20]

0x6E

(110)

1 to 24

2

- - - -

10002

uint
RWES

[`S2;A]
[ SZ.A]

Action (1 to 24)

Source Zone A

Set the zone of the function

selected above.

0 to 16

0

2192
[offset 20]

0x6E

(110)

1 to 24

7

- - - -

10007

uint
RWES

[`LEu]
[ LEv]

Action (1 to 24)

Active Level

Set the action that will be

considered a true state.

[LoW]

Low (53)

[high]

High (37)

High

2180
[offset 20]

0x6E

(110)

1 to 24

1

112

10001

uint
RWES

[LooP]
[`Set]
Control Loop Menu

[SFn;A]
[SFn.A]

Control Loop (1 to 16)

Source Function A

Set the type of function

that will be used for this

source.

[``Ai]

Analog Input (142)

[``Pu]

Process Value (241)

Analog

Input

4156

[offset 70]

0x97 (151)

1 to 16

0x1D (29)

- - - -

8050

uint
RWE

Note:

Some values will be rounded off to fit in the four-character display.

Full values can be read with other interfaces.

Note:

If there is only one instance of a menu, no submenus will appear.

** These parameters/prompts are available in these menus with firmware revisions 6.0 and

above.

R: Read

W: Write

E:

EEPROM

S:

User

Set