Watlow EZ-ZONE RMH User Manual

Page 64

background image

Watlow EZ-ZONE

®

RMH Module

61

Chapter 4 Setup Page

RM High Density Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[``dB]
[ db]

Control Loop (1 to 16)

Dead Band

Set the offset to the

proportional band. With

a negative value, both

heating and cooling out-

puts are active when the

process value is near the

set point. A positive value

keeps heating and cooling

outputs from fighting each

other.

-1,000.0 to 1,000.0 °F or

units

-555.556 to 555.556 °C

0.0

4118
[offset 70]

0x97

(151)

1 to 16

0xA (10)

61

8008

float

RWES

[t;tUn]
[t.tUn]

Control Loop (1 to 16)

TRU-TUNE+™ Enable

Enable or disable the

TRU-TUNE+™ adaptive

tuning feature.

[``no]

No (59)

[`YES}

Yes (106)

No

4130
[offset 70]

0x97 (151)

1 to 16

0x10 (16)

- - - -

8022

uint

RWES

[t;bnd]
[t.bnd]

Control Loop (1 to 16)

TRU-TUNE+™ Band

Set the range, centered on

the set point, within which

TRU-TUNE+™ will be in

effect. Use this function

only if the controller is un-

able to adaptive tune auto-

matically.

0 to 100 °F or units

0 to 55 °C

0

4132
[offset 70]

0x97 (151)

1 to 16

0x11 (17)

- - - -

8034

uint

RWES

[`t;gn]
[ t.gn]

Control Loop (1 to 16)

TRU-TUNE+™ Gain

Select the responsiveness

of the TRU-TUNE+™

adaptive tuning calcula-

tions. More responsiveness

may increase overshoot.

1 to 6

3

4134
[offset 70]

0x97 (151)

1 to 16

0x12 (18)

- - - -

8035

uint

RWES

[A;tSP]
[A.tSP}

Control Loop (1 to 16)

Autotune Set Point

Set the set point that the

autotune will use, as a

percentage of the current

set point.

50.0 to 200.0%

90.0

4138
[offset 70]

0x97

(151)

1 to 16

0x14 (20)

- - - -

8025

float

RWES

[t;Agr]
[t.Agr]

Control Loop (1 to 16)

Autotune Aggressiveness

Select the aggressiveness

of the autotuning calcula-

tions.

[Undr]

Under damped (99)

[Crit]

Critical damped (21)

[OuEr]

Over damped (69)

Critical

4136
[offset 70]

0x97 (151)

1 to 16

0x13 (19)

- - - -

8024

uint

RWES

[`p;dl]
[ P.dL]

Control Loop (1 to 16)

Peltier Delay

Set a value that will cause

a delay when switching

from heat mode to cool

mode.

0.0 to 5.0 seconds

0.0

4154
[offset 70]

0x97 (151)

1 to 16

0x1C (28)

- - - -

8051

float

RWES

Note:

Some values will be rounded off to fit in the four-character display.

Full values can be read with other interfaces.

Note:

If there is only one instance of a menu, no submenus will appear.

** These parameters/prompts are available in these menus with firmware revisions 6.0 and

above.

R: Read

W: Write

E:

EEPROM

S:

User