Watlow EZ-ZONE RMH User Manual

Page 63

background image

Watlow EZ-ZONE

®

RMH Module

60

Chapter 4 Setup Page

RM High Density Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[`Si;A]
[ Si.A]

Control Loop (1 to 16)

Source Instance A

Set the instance of the

function selected above.

1 to 16

1

- - - -

- - - -

- - - -

8021

uint
R

[`h;Ag]
[ h.Ag]

Control Loop (1 to 16)

Heat Algorithm

Set the heat control

method.

[`oFF]

Off (62)

[`Pid]

PID (71)

[on;of]

On-Off (64)

PID

4104
[offset 70]

0x97 (151)

1 to 16

3

62

8003

uint

RWES

[`C;Ag]
[ C.Ag]

Control Loop (1 to 16)

Cool Algorithm

Set the cool control method.

[`oFF]

Off (62)

[`Pid]

PID (71)

[on;of]

On-Off (64)

Off

4106
[offset 70]

0x97 (151)

1 to 16

4

63

8004

uint

RWES

[`C;Cr]
[ C.Cr]

Control Loop (1 to 16)

Cool Output Curve

Select a cool output curve

to change the responsive-

ness of the system.

[`oFF]

Off (62)

[`Cr;A]

Non-linear Curve 1

(214)

[`Cr;b]

Non-linear Curve 2

(215)

Off

4108
[offset 70]

0x97 (151)

1 to 16

5

- - - -

8038

uint

RWES

[`h;Pb]
[ h.Pb]

Control Loop (1 to 16)

Heat Proportional Band

Set the PID proportional

band for the heat outputs.

0.001 to 9,999.000°F or units

0.001 to 5,555.000°C

25.0°F or

units

14.0°C

4110
[offset 70]

0x97

(151)

1 to 16

6

55

8009

float

RWES

[`h;hy]
[ h.hy]

Control Loop (1 to 16)

Heat Hysteresis

Set the control switching

hysteresis for on-off con-

trol. This determines how

far into the “on” region

the process value needs

to move before the output

turns on.

0.001 to 9,999.000°F or units

0.001 to 5,555.000°C

3.0°F or

units

2.0°C

4120
[offset 70]

0x97

(151)

1 to 16

0xB (11)

56

8010

float

RWES

[`C;Pb]
[ C.Pb]

Control Loop (1 to 16)

Cool Proportional Band

Set the PID proportional

band for the cool outputs.

0.001 to 9,999.000°F or units

0.001 to 5,555.000°C

25.0°F or

units

14.0°C

4112
[offset 70]

0x97

(151)

1 to 16

7

57

8012

float

RWES

[`C;hy]
[ C.hy]

Control Loop (1 to 16)

Cool Hysteresis

Set the control switching

hysteresis for on-off con-

trol. This determines how

far into the “on” region

the process value needs

to move before the output

turns on.

0.001 to 9,999.000°F or units

0.001 to 5,555.000°C

3.0°F or

units

2.0°C

4122
[offset 70]

0x97

(151)

1 to 16

0xC (12)

58

8013

float

RWES

[``ti]
[ ti]

Control Loop (1 to 16)

Time Integral

Set the PID integral for

the outputs.

0 to 9,999 seconds per repeat 180 sec-

onds per

repeat

4114
[offset 70]

0x97

(151)

1 to 16

8

59

8006

float

RWES

[``td]
[ td]

Control Loop (1 to 16)

Time Derivative

Set the PID derivative

time for the outputs.

0 to 9,999 seconds

0 seconds 4116

[offset 70]

0x97

(151)

1 to 16

9

60

8007

float

RWES

Note:

Some values will be rounded off to fit in the four-character display.

Full values can be read with other interfaces.

Note:

If there is only one instance of a menu, no submenus will appear.

** These parameters/prompts are available in these menus with firmware revisions 6.0 and

above.

R: Read

W: Write

E:

EEPROM

S:

User

Set