Troubleshooting alarms, errors and module issues – Watlow EZ-ZONE RMH User Manual
Page 150
Watlow EZ-ZONE
®
RMH Module
•
147
•
Appendix
Troubleshooting Alarms, Errors and Module Issues
Indication
Description
Possible Cause(s)
Corrective Action
Alarm won’t clear or
reset
Alarm will not clear or reset
with keypad or digital input
• Alarm latching is active
• Alarm set to incorrect output
• Alarm is set to incorrect source
• Sensor input is out of alarm set point
range
• Alarm set point is incorrect
• Alarm is set to incorrect type
• Digital input function is incorrect
• Reset alarm when process is within
range or disable latching
• Set output to correct alarm source
instance
• Set alarm source to correct input in-
stance
• Correct cause of sensor input out of
alarm range
• Set alarm set point to correct trip
point
• Set alarm to correct type: process, de-
viation or power
• Set digital input function and source
instance
Alarm won’t occur
Alarm will not activate output • Alarm silencing is active
• Alarm blocking is active
• Alarm is set to incorrect output
• Alarm is set to incorrect source
• Alarm set point is incorrect
• Alarm is set to incorrect type
• Disable alarm silencing, if required
• Disable alarm blocking, if required
• Set output to correct alarm source
instance
• Set alarm source to correct input in-
stance
• Set alarm set point to correct trip
point
• Set alarm to correct type: process, de-
viation or power
Alarm Error
[AL;E1]
[AL;E2]
[AL;E3]
[AL;E4]
[AL;E5]
[AL;E6]
[AL;E7]
[AL;E8]
[AL;E9]
[AL;10]
[AL;11]
[AL;12]
[AL;13]
[AL;14]
[AL;15]
[AL;16]
[AL;17]
[AL;18]
[AL;19]
[AL;20]
[AL;21]
[AL;22]
[AL;23]
[AL;24]
Alarm state cannot be deter-
mined due to lack of sensor
input
• Sensor improperly wired or open
• Incorrect setting of sensor type
• Calibration corrupt
• Correct wiring or replace sensor
• Match setting to sensor used
• Check calibration of controller
Alarm Low
[AL;L1]
[AL;L2]
[AL;L3]
[AL;L4]
[AL;L5]
[AL;L6]
[AL;L7]
[AL;L8]
[AL;L9] [AL;10]
[AL;11]
[AL;12]
[AL;13]
[AL;14]
[AL;15]
[AL;16]
[AL;17]
[AL;18]
[AL;19]
[AL;20]
[AL;21]
[AL;22]
[AL;23]
[AL;24]
Sensor input below low alarm
set point
• Temperature is less than alarm set
point
• Alarm is set to latching and an alarm
occurred in the past
• Incorrect alarm set point
• Incorrect alarm source
• Check cause of under temperature
• Clear latched alarm
• Establish correct alarm set point
• Set alarm source to proper setting
Alarm High
[AL;h1}
[AL;h2]
[AL;h3]
[AL;h4]
[AL;h5}
[AL;h6]
[AL;h7]
[AL;h8]
[AL;h9] [AL;10]
[AL;11]
[AL;12]
[AL;13]
[AL;14]
[AL;15]
[AL;16]
[AL;17]
[AL;18]
[AL;19]
[AL;20]
[AL;21]
[AL;22]
[AL;23]
[AL;24]
Sensor input above high
alarm set point
• Temperature is greater than alarm
set point
• Alarm is set to latching and an alarm
occurred in the past
• Incorrect alarm set point
• Incorrect alarm source
• Check cause of over temperature
• Clear latched alarm
• Establish correct alarm set point
• Set alarm source to proper setting