Watlow EZ-ZONE RMH User Manual
Page 55

Watlow EZ-ZONE
®
RMH Module
•
52
•
Chapter 4 Setup Page
RM High Density Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[`P;EE]
[ P.EE]
Analog Input (1 to 16)
Process Error Enable
Turn the Process Error
Low feature on or off.
[`off]
Off (62)
[Low]
Low (53)
Off
438
[offset 90]
0x68 (104)
1 to 16
0x1E (30)
10
4030
uint
RWE
[`P;EL]
[ P.EL]
Analog Input (1 to 16)
Process Error Low Value
If the process value drops
below this value, it will
trigger an input error.
-100.0 to 1,000.0
0.0
440
[offset 90]
0x68 (104)
1 to 16
0x1F (31)
11
4031
float
RWE
[``t;C]
[ t.C]
Analog Input (1 to 16)
Thermistor Curve
Select a curve to apply to
the thermistor input.
[```A]
Curve A (1451)
[```b]
Curve B (1452)
[```C]
Curve C (1453)
[CUSt]
Custom (180)
Curve A
454
[offset 90]
0x68 (104)
1 to 16
0x26 (38)
- - - -
4038
uint
RWE
[``r;r]
[ r.r]
Analog Input (1 to 16)
Resistance Range
Set the maximum resis-
tance of the thermistor
input.
[```5]
5K (1448)
[``10]
10K (1360)
[``20]
20K (1361)
[``40]
40K (1449)
40K
452
[offset 90]
0x68 (104)
1 to 16
0x25 (37)
- - - -
4037
uint
RWE
[`FiL]
[ FiL]
Analog Input (1 to 16)
Filter
Filtering smooths out the
process signal to both the
display and the input. In-
crease the time to increase
filtering.
0.0 to 60.0 seconds
0.5
406
[offset 90]
0x68 (104)
1 to 16
0xE (14)
12
4014
float
RWE
[`i;Er]
[ i.Er]
Analog Input (1 to 16)
Error Latching
Turn input error latching
on or off. If latching is on,
errors must be manually
cleared.
[`off]
Off (62)
[``on]
On (63)
Off
434
[offset 90]
0x68 (104)
1 to 16
0x1C (28)
- - - -
4028
uint
RWE
[`dEC]
[ dEC]
Analog Input (1 to 16)
Display Precision
Set the precision of the dis-
played value.
[```0]
Whole (105)
[``0;0]
Tenths (94)
[`0;00]
Hundredths (40)
[0;000]
Thousandths (96)
Whole
418
[offset 90]
0x68 (104)
1 to 16
0x14 (20)
- - - -
4020
uint
RWE
[`i;Ca]
[ i.CA]
Analog Input (1 to 16)
Calibration Offset
Offset the input reading to
compensate for lead wire
resistance or other factors
that cause the input read-
ing to vary from the actual
process value.
-1,999.000 to 9,999.000°F or
units
-1,110.000 to 5,555.000°C
0.0
402
[offset 90]
0x68 (104)
1 to 16)
0x0C (12)
- - - -
4012
float
RWE
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E:
EEPROM
S:
User
Set