Digital input/output menu – Watlow EZ-ZONE RMH User Manual
Page 59

Watlow EZ-ZONE
®
RMH Module
•
56
•
Chapter 4 Setup Page
RM High Density Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[p;unt]
[P.unt]
Process Value (1 to 16)
Pressure Units
Set the units that will be
applied to the source.
[`psi]
Pounds per Square
Inch (1671)
[mbr]
Millibar (1672)
[torr]
Torr (1673)
[pasc]
Pascal (1674)
[atm]
Atmosphere (1675)
PSI
8274
[offset 70]
0x7E
(126)
1 to 16
0x1C (28)
- - - -
26028
uint
RWES
[a;unt]
[A.unt]
Process Value (1 to 16)
Altitude Units
Set the units that will be
applied to the source.
[`Hft]
Kilofeet (1677)
[``ft]
Feet (1676)
HFt
8276
[offset 70]
0x7E
(126)
1 to 16
0x1D (29)
- - - -
26029
uint
RWES
[`b;pr]
[ b.Pr]
Process Value (1 to 16)
Barometric Pressure
Set the units that will be
applied to the source.
10.0 to 16.0
14.7
8278
[offset 70]
0x7E
(126)
1 to 16
0x1E (30)
- - - -
26030
float
RWES
[`Fil]
[ FiL]
Process Value (1 to 16)
Filter
Filtering smooths out the
output signal of this func-
tion block. Increase the
time to increase filtering.
0.0 to 60.0 seconds
0.0
8270
[offset 70]
0x7E
(126)
1 to 16
0x1A (26)
- - - -
26026
float
RWES
[`dio]
[`Set]
Digital Input/Output Menu
[`dir]
[ dir]
Digital Input/Output (1
to 12)
Direction
Set this function to operate
as an input or output.
[OtPt]
Output (68)
[``in]
Input Voltage (193)
[iCon]
Input Dry Contact
(44)
Output
1820
[offset 30]
0x6A
(106)
1 to 12
1
72
6001
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E:
EEPROM
S:
User
Set