Watlow EZ-ZONE RMH User Manual
Page 81

Watlow EZ-ZONE
®
RMH Module
•
78
•
Chapter 4 Setup Page
RM High Density Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[`S2;A]
[ SZ.A]
Counter (1 to 24)
Source Zone A
Set the zone of the function
selected above.
0 to 16
0
12228
[offset 40]
0x82 (130)
1 to 24
5
- - - -
30005
uint
RWES
[sas;A]
[SAS.A]
Counter (1 to 24)
Source Active State A
Set what output state will
indicate on.
[high]
High (37)
[LoW]
Low (53)
[both]
Both (130)
High
12240
[offset 40]
0x82 (130)
1 to 24
0x0B (11)
- - - -
30011
uint
RWES
[SFn;B]
[SFn.b]
Counter (1 to 24)
Source Function B
Set the type of function
that will be used for the
counter load signal.
[nonE]
None (61)
[ALM]
Alarm (6)
[`CPE]
Compare (230)
[`Ctr]
Counter (231)
[`dio]
Digital I/O (1142)
[Ent;A]
Profile Event Out A
(233)
[Ent;b]
Profile Event Out B
(234)
[Ent;C]
Profile Event Out C
(235)
[Ent;d]
Profile Event Out D
(236)
[Ent;E]
Profile Event Out E
(247)
[Ent;F]
Profile Event Out F
(248)
[Ent;g]
Profile Event Out G
(249)
[Ent;h]
Profile Event Out H
(250)
[`FUn]
Function Key (1001)
[`lgC]
Logic (239)
[tMr]
Timer (244)
[`uAr]
Variable (245)
None
12222
[offset 40]
0x82 (130)
1 to 24
2
- - - -
30002
uint
RWES
[`Si;B]
[ Si.b]
Counter (1 to 24)
Source Instance B
Set the instance of the
function selected above.
1 to 250
1
12226
[offset 40]
0x82 (130)
1 to 24
4
- - - -
30004
uint
RWES
[`S2;B]
[ SZ.b]
Counter (1 to 24)
Source Zone B
Set the zone of the function
selected above.
0 to 16
0
12230
[offset 40]
0x82 (130)
1 to 24
6
- - - -
30006
uint
RWES
[sas;b]
[SAS.b]
Counter (1 to 24)
Source Active State B
Set what output state will
indicate on.
[high]
High (37)
[LoW]
Low (53)
High
12242
[offset 40]
0x82 (130)
1 to 24
0xC (12)
- - - -
30012
uint
RWES
[LoAd]
[LoAd]
Counter (1 to 24)
Load Value
Set the counter's initial
value.
0 to 9,999
0
12244
[offset 40]
0x82 (130)
1 to 24
(13)
157
30013
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E:
EEPROM
S:
User
Set