Alarm menu – Watlow EZ-ZONE RMH User Manual
Page 71
Watlow EZ-ZONE
®
RMH Module
•
68
•
Chapter 4 Setup Page
RM High Density Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[`r;Lo]
[ r.Lo]
Output Process(1 to 3, 7
to 9)
Range Low **
Use to set the minimum
value in process units. This
will correspond with the
Scale Low value.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
0.0°F or
units
-18°C
16560
[offset 60]
0x76 (118)
1-3, 7-9
0xB (11)
- - - -
18011
float
RWES
[`r;hi]
[ r.hi]
Output Process (1 to 3, 7
to 9)
Range High **
Use to set the maximum
value in process units. This
will correspond with the
Scale High value.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
100°F or
units
38°C
16562
[offset 60]
0x76 (118)
1-3, 7-9
0xC (12)
- - - -
18012
float
RWES
[`o;CA]
[ o.CA]
Output Process (1 to 3, 7
to 9)
Calibration Offset **
Set an offset value for a
process output.
-1,999.000 to 9,999.000°F or
units
-1,110.000 to 5,555.000°C
0.0°F or
units
0.0°C
16552
[offset 60]
0x76 (118)
1-3, 7-9
7
- - - -
18007
float
RWES
[Alm]
[`Set]
Alarm Menu
[`A;ty]
[ A.ty]
Alarm (1 to 24)
Alarm Type
Select whether the alarm
trigger is a fixed value or
will track the set point.
[`oFF]
Off (62)
dE;AL]
Deviation Alarm (24)
[PR;AL]
Process Alarm (76)
Off
2688
[offset 60]
0x6D
(109)
1 to 24
0xF (15)
20
9015
uint
RWES
[`Sr;A]
[ Sr.A]
Alarm (1 to 24)
Alarm Source
Select what will trigger
this alarm.
[none]
None (61)
[``Ai]
Analog Input (142)
[CUrr]
Current (22)
[PWr]
Power, Control Loop
(73)
[`lnr]
Linearization (238)
[mat]
Math (240)
[``Pu]
Process Value (241)
[`uAr]
Variable (245)
[`Cu;r]
Current Read (179)
Analog
Input
2692
[offset 60]
0x6D
(109)
1 to 24
0x11 (17)
21
9017
uint
RWES
[`is;A]
[ iS.A]
Alarm (1 to 24)
Alarm Source Instance A
Set the instance of the
function selected above.
1 or 250
1
2694
[offset 60]
0x6D
(109)
1 to 24
0x12 (18)
22
9018
uint
RWES
[`S2;A]
[ SZ.A]
Alarm (1 to 24)
Alarm Source Zone A
Set the zone of the function
selected above.
0 or 16
0
2708
[offset 60]
0x6D
(109)
1 to 24
0x19 (25)
- - - -
9025
uint
RWES
[loop]
[loop]
Alarm (1 to 24)
Control Loop
Select the loop when de-
viation alarm is selected
above.
1 to 16
1
2704
[offset 60]
0x6D
(109)
1 to 24
0x17 (23)
23
9023
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E:
EEPROM
S:
User
Set