beautypg.com

IAI America PCON-CFA User Manual

Page 39

background image

2. ACON-C/CG,

PCON-C/CG



31


(2) I/O signal assignments for each axis

An I/O signal of each axis consists of 16 bytes of I/O addresses.

z Control signals and status signals are bit ON/OFF signals.

z The target position and current position are both 4 bytes (32-bit) binary data. Although values from -999999 to

+999999 (unit: 0.01 mm) can be handled by the PLC, set position data within the software stroke range (0 up
to the effective stroke length) of the applicable actuator.

z Set a desired positioning band. The positioning band is 4 bytes (32-bit) binary data and values from 1 to

+999999 (unit: 0.01 mm) can be handled by the PLC.

z The speed is 2 bytes (16-bit) binary data. Although values from 0 to +65535 (unit: 1.0 mm/sec) can be handled

by the PLC, set a value not exceeding the maximum speed of the applicable actuator.

z The acceleration/deceleration is 2 bytes (16-bit) binary data. Although values from 1 to 300 (unit: 0.01 G) can

be handled by the PLC, set a value not exceeding the maximum acceleration and maximum deceleration of
the applicable actuator.

z The push-current limiting value is 2 bytes (16-bit) binary data. Although values from 0 (0%) to 255 (100%) can

be handled by the PLC, set a value within the specifiable range of push-current limiting values of the
applicable actuator (refer to the catalog or operation manual for the actuator).







z The command current is 4 bytes (32-bit) binary data (unit: 1 mA).

z The current position is 4 bytes (32-bit) binary data (unit: 0.01 mm/sec).

z The alarm code is 2 bytes (16-bit) binary data.

Set value

Push-current
limiting value

127

This manual is related to the following products: