4. SCON-CA


120



[6] Half direct mode 2: In this mode, the actuator is operated by specifying the speed, acceleration/deceleration

and push current, in addition to the target position, directly as values.
Unlike in mode [3], command current cannot be read in this mode. However, load cell
data can be read instead. This mode also supports force control.
Number of occupied bytes: 16 bytes

Target position: 100.00 mm
Positioning band: 0.10 mm
Speed specification:
100.0 mm/sec
Acceleration/deceleration:
0.30 G
Push current: 50%

SCON-CA supporting
MECHATROLINK

Actuator


[7] Remote I/O mode 3: In this mode, the actuator is operated by MECHATROLINK instead of PIO (24 V I/O).

This mode provides all functions available in mode [1], plus the current position read
function and load cell data read function.
Number of occupied bytes: 12 bytes














.



SCON-CA not supporting

MECHATROLINK

PLC

Flat cable

PIO connection

SCON-CA supporting

MECHATROLINK

PLC

MECHATROLINK connection

Communication