9 mechatrolink parameters – IAI America PCON-CFA User Manual

Page 118

background image

3. SCON-CA/CF

A


110


3.9 MECHATROLINK

Parameters

The parameters relating to MECHATROLINK are parameter Nos. 84 to 87 and 90.

Category: C: External interface parameter

No. Category Symbol

Name

Factory

default

1

~

83

For parameter Nos. 1 to 83, refer to the operation
manual for the controller.

84

C

FMOD

Fieldbus operation mode

0

85

C

NADR

Fieldbus node address

97

86 C FBRS

Fieldbus

baud

rate

2

87 C NYTP

Network

type

5

90

C

FMIO

Fieldbus I/O format

3

159

C

FBVS

FB half direct mode speed unit

0

z Fieldbus operation mode (No. 84 FMOD)
Specify a desired operation mode in parameter No. 84 using a value between 0 and 4.

* 3 cannot be specified

Set value of

parameter No. 84

Mode name

Description

0 (factory setting) Remote I/O mode

The actuator is operated by PIOs (24-V I/Os) via MECHATROLINK.

1

Position/simple direct
mode

The target position can be specified directly as a value or using a value
in the position data table. Other values required for operation are set in
the position data table.

2

Half direct mode

Operate the actuator by specifying the speed, acceleration/deceleration
and push-current value, in addition to the target position, directly using
values.
Cannot be used if parameter No. 86 Fieldbus baud rate is set to 0 or 1
(17-byte mode)

4

Remote I/O mode 2

The current-position and current-speed read functions are added to the
functions available in the remote I/O mode.

z Fieldbus node address (No. 85 NADR)
Specify the slave number of the remote station in parameter No. 85.
Setting range: 97 to 127 (The factory setting is 97.)

z Fieldbus baud rate (No. 86 FBRS)
Specify the baud rate to Parameter No. 86.

Set value of parameter

No. 86

Baud rate

Data length

0

MECHATROLINK-I

4 Mbps

17 bytes

1

MECHATROLINK-II

10 Mbps

17 bytes

2 (factory setting)

MECHATROLINK-II

10 Mbps

32 bytes