12. Inspection/Maintenance

Cover (base)

Battery

(for axis 1)

Battery connector 3

(for axis 3)

Battery

(for axis 3)

Battery connector 2

(for axis 2)

Battery (for axis 2)

Battery connector 4

(for axis 4)

Battery

(for axis 4)

Battery connector 1

(for axis 1)

[1] 6-M3 X 8

Battery holder

12.2.3 Replacement

Procedure

IX-NNW50

……H/60……H/70……H/80……H

(1) Remove the countersunk head screws (6 pcs) [1] and take out the cover (base).
(2) Remove the batteries from the battery holder.
(3) Unplug the BAT connector and connect a new battery.

x After removing the old batteries, quickly connect new batteries (roughly within 5 minutes x

number of batteries).

x If new batteries are not connected for a longer period, the rotation data will be lost and an

absolute reset will become necessary.

x Replace batteries one axis at a time. If the batteries for all axes are replaced at once, the work

may not be completed within the specified time.

(4) Install the batteries into the battery holder.