Mv/v, Chapter – Advantech Data Acquisition Modules ADAM 4000 User Manual
Page 62

Chapter
3
Chapter 3 I/O Modules 3-35
Isolation Voltage
3000 V
DC
Fault and over-voltage protection
Withstands over voltage up to ±35 V
Sampling Rate
10 sample/sec (total)
Input Impedance
Voltage: 20 MΩ, Current: 120Ω
Accuracy ±0.1%
or
better
Power Consumption
0.8 W @ 24V
DC
I/O Connector Type
10 pin plug-in terminal
Table 3-4 Technical specification of ADAM-4018+
Application Wiring
Figure 3-30 Current Input Wiring Diagram of ADAM-4017
Vin0-
Vin0+
11
V
-
+
mV/V
Figure 3-31(a) ADAM-4017 Differential Input Wiring Diagram (Ch0 ~ Ch5)