beautypg.com

Advantech Data Acquisition Modules ADAM 4000 User Manual

Page 225

background image

Chapter

6


6-11 ADAM 4000 Series User’s Manual

$AA0

Name

4 mA Calibration command

Description

Stores the current output value 4 mA for reference in the
specified address in analog output module.

Syntax

$AA0(cr)

$

is a delimiter character.

AA

(range 00-FF) represents the 2-character hexadecimal

address whose data are to be sent.

0

is the 4 mA Calibration command.

(cr)

is the terminating character, carriage return (0Dh).

Response

!AA(cr)

if the command was valid.

?AA(cr)

if an invalid command was issued.

There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.

!

delimiter character indicates that a valid command was

received.

?

delimiter character indicates that the command was

invalid.

AA

(range 00-FF) represents the responding 2-character

hexadecimal address of the analog output module.

(cr)

is the terminating character, carriage return (0Dh).

Before issuing the 4 mA Calibration command, the analog
output module should be trimmed to the correct value with
the Trim Calibration command. A millimeter or a resistor
and voltmeter should be connected to the module’s output.
(Please refer to the analog output module’s Trim
Calibration command and Chapter 8, Calibration, for a
detailed description.)