Advantech Data Acquisition Modules ADAM 4000 User Manual
Page 276

Chapter
7
7-41 ADAM 4000 Series User’s Manual
$AAAG
Name
Set Gate Mode command
Description
Request the specified counter/frequency module to set its
gate to one of the three states, high, low or disabled.
Syntax
$AAAG(cr)
$
is a delimiter character.
AA
(range 00-FF) represents the 2-character hexadecimal
address that you will access to.
A
is the Gate Mode command.
G
determines the gate mode:
G = 0 the gate is low
G = 1 the gate is high
G = 2 the gate is disabled
(cr
) is the terminating character, carriage return (0Dh).
Response
!AA(cr)
if the command is valid.
There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.
!
is a delimiter character which indicates a valid command.
AA
(range 00-FF) represents the 2-character hexadecimal
address of the module.
(cr)
is the terminating character, carriage return (0Dh).
Example
command: $01A1(cr)
response: !01(cr)
The command requests the counter/frequency module at
address 01 to set its gate high. The module will reply with
an address indicating that it has executed the command.
4080, 4080D