Advantech Data Acquisition Modules ADAM 4000 User Manual
Page 295

Digital I/O and Relay Output
Counter/Frequency Command Set
7-60 ADAM 4000 Series User’s Manual
7.2.4 Digital Output and Alarm Command Set
Command Syntax
Command Name
Description
I/O Module
@AAPN(data)
Set Initial Count Value
of Counter N
Sets the inital count value of
the module for counter 0 or
counter 1
4080
@AAGN
Read Initial Count
Value of Counter N
Read the initial count value of
counter 0 or counter 1
4080
@AAEAN Enable
Alarm
of
Counter N
Enable alarm for the specified
counter 0 or counter 1
4080
@AADAN Disable
Alarm
of
Counter N
Disable alarm for the specified
counter 0 or counter 1
4080
@AAPA(data) Set
Alarm
Limit
Value
of Counter 0
Download the alarm limit value
for counter 0 of the specified
module
4080
@AASA(data) Set
Alarm
Limit
Value
of Counter 1
Download the alarm limit value
for counter 1 of the specified
module
4080
@AARP Read
Alarm
Limit
Value of Counter 0
Ask the module to return the
alarm limit value of counter 0
4080
@AARA Read
Alarm
Limit
Value of Counter 1
Ask the module to return the
alarm limit value of counter 1
4080
@AADO(data) Set
Digital
Output
Values
Set the values of the module's
two digital outputs (ON or OFF)
4080,
4080D
@AADI Read
Digital
Output
and Alarm Status
Ask the addressed module to
return the state of its two digital
output channels and the status
of its alarm
4080,
4080D
(Continued on next page)