@AAEAT

Name Enable

Alarm

command

Description

The counter module is instructed to enable its alarm for
counter 0 in either Latching or Momentary mode.

Syntax

@AAEAT(cr)

@

is a delimiter character.

AA

(range 00-FF) represents the 2-character hexadecimal

address of the module.

EA

is the Enable Alarm command.

T

indicates the alarm type and can have the value M =

Momentary alarm state, or L = Latching alarm state.

(cr)

represents terminating character, carriage return (0Dh).

Response

!AA(cr)

if the command was valid

There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.

!

is a delimiter character which indicates a valid command.

AA

represents the 2-character hexadecimal address of the

module.

(cr)

represents terminating character, carriage return (0Dh)

Example command:

@03EAL(cr)

response: !03(cr)

The counter module at address 03h is instructed to enable
its alarm for counter 0 in Latching mode.

The module confirms that the command has been received.

NOTICE: A counter module requires a maximum of two seconds after it

has received an Enable Alarm command to let the settings take
effect. During this time, the module can not be addressed to
perform any other actions.