Command Set
4-34 ADAM 4000 Series User’s Manual
ADAM-4060/4068 Command Table
Command Syntax
Command Name
Command Description
Page
No.
%AANNTTCCFF
Configuration
Sets address, baud rate, and/or
checksum status, to a digital I/O
module
7-4
$AA6
Digital Data In
Returns the values of the digital I/O
channels of the addressed module
7-6
#AABB(data)
Digital Data Out
Writes specified values to either a
single channel or all channels
simultaneously
7-8
#** Synchronized
Sampling
Orders all digital I/O modules to
sample their input values and store
them in a special register
7-11
$AA4 Read
Synchronized
Data
Return the value of a specified digital
I/O module that was stored after an
#** command was issued
7-12
$AA2 Configuration
Status
Returns the configuration parameters
of a specified digital I/O module
7-14
$AA5
Reset Status
Indicates whether a specified digital
I/O module was reset after the last
time the $AA5 command was issued
7-16
$AAF Read
Firmware
Version
Return the firmware version code
from the specified digital I/O module
7-18
$AAM
Read Module Name
Return the module name from the
specified digital I/O module
7-19
$AAX0TTTTDDDD Write Safty Value
Force the DO channels to safety
status when communication is
time-out and over pre-defined period.
7-21
$AAX1
Read Safty Value
Read the time-out setting and
pre-defined safety status of DO
channels.
7-22
$AAX2
Read Safty Flag
Requests the Safty Flag of the
addressed digital I/O module to see
whether the safety value has been
executed since Write Safety Value
command was set.
7-23