Technical Specifications
A-16 ADAM 4000 Series User’s Manual
A.7 ADAM-4018/4018+ 8-channel Analog Input Module
Table A-9 ADAM-4018/4018+ Specifications
AI channel number
ADAM-4018:
6 differential and 2 single-ended
ADAM-4018+:
8 differential
Input type
Thermocouple with mV, V, or mA
Input range
J, K, T, E, R, S and B Thermocouple
ADAM-4018:
±15 mV, ±50 mV, ±100 mV, ±500 mV,
±1 V, ±2.5 V and ±20 mA
ADAM-4018+:
±20 mA and 4~20 mA
Output
speed (bps)
Maximum distance
RS-485 (2-wire)
1200, 2400, 4800, 9600, 19.2K, 38.4K,
57.6K, 115.2K
4000 ft. (1200 m)
Isolation voltage
3000 V
DC
Resolution 16-bit
Sampling rate
10 samples/second (total)
Bandwidth 13.1
Hz
Accuracy
±0.1% or better
Zero drift
±6 μV/℃
Span drift
±25 ppm/℃
CMR @ 50/60 Hz
120 dB
NMR @ 50/60 Hz
100 dB
Input impedance
Voltage: 20 MΩ, Current: 120 Ω
Support protocol
ADAM ASCII
(ADAM-4018 & 4108+)
MODBUS/RTU
(ADAM-4018+ only)
Watchdog timer
ADAM-4018:
System (1.6 second)
ADAM-4018+:
System (1.6 second) and communication
Power requirements +10 to +30 V
DC
(non-regulated)
Power consumption 0.8 W @ 24 V
DC
Burn-out detection
All T/C input
(ADAM-4018+ only)