Chapter

7


7-45 ADAM 4000 Series User’s Manual

$AA5NS

Name Start/Stop

Counter

command

Description

Request the counter/frequency module to start or stop the
counting for either counter 0 or counter 1.

Syntax

$AA5NS(cr)

$

is a delimiter character.

AA

(range 00-FF) represents the 2-character hexadecimal

address that you will access to.

5

is the Start/Stop Counter command.

N

determines the counter that should be either enabled or

disabled.

N = 0 represents counter 0
N = 1 represents counter 1

S

represents the counter status.

S = 0 stops counting
S = 1 starts counting

(cr)

is the terminating character, carriage return (0Dh).

Response

!AA(cr)

if the command is valid. There is no response if

the module detects a syntax or communication error, or
even if the specified address does not exist.

!

is a delimiter character which indicates a valid command.

AA

(range 00-FF) represents the 2-character hexadecimal

address of a counter input module.

(cr)

is the terminating character, carriage return (0Dh).

Example command:

$06501(cr)

response: !06(cr)

The command requests the counter 0 of counter/frequency
module at address 06 to start. The addressed module replies
with its address indicating that the command has been
executed. Counter 0 has started.

4080, 4080D