Command set – Advantech Data Acquisition Modules ADAM 4000 User Manual
Page 133

Command Set
4-30 ADAM 4000 Series User’s Manual
ADAM-4053 Command Table
Command Syntax
Command Name
Command Description
Page
No.
%AANNTTCCFF
Configuration
Sets address, baud rate, and/or
checksum status, to a digital I/O
module
7-4
$AA6
Digital Data In
Returns the values of the digital I/O
channels of the addressed module
7-6
#** Synchronized
Sampling
Orders all digital I/O modules to
sample their input values and store
them in a special register
7-11
$AA4 Read
Synchronized
Data
Return the value of a specified
digital I/O module that was stored
after an #** command was issued
7-12
$AA2
Configuration Status
Returns the configuration
parameters of a specified digital I/O
module
7-14
$AA5
Reset Status
Indicates whether a specified digital
I/O module was reset after the last
time the $AA5 command was
issued
7-16
$AAF Read
Firmware
Version
Return the firmware version code
from the specified digital I/O module
7-18
$AAM
Read Module Name
Return the module name from the
specified digital I/O module
7-19