Chapter 8 Calibration 8-15
Module: ADAM-4016
1. Apply power to the strain gauge input module and let it warm up for
about 30 minutes.
2. Assure that the module is correctly installed. Then, connect a
voltmeter to the screw terminals of the module.
Exc-
Voltmeter
-
+
Exc+
Ii
n
-
Ii
n
+
Vin-
Vin+
ADAM-4016
Figure 8-7 Setup for Voltage Output Calibration
3. Execute the Zero Calibration command. This is done through the
ADAM utility software. (Please see "A/O 0V Calibration" option in
the Calibration sub-menu of the ADAM utility software.)
Figure 8-8 Zero Calibration