Command Set


4-20 ADAM 4000 Series User’s Manual


ADAM-4018M Command Table

Command Syntax

Command Name

Command Description

Page
No.

%AANNTTCCFF

Configuration

Set the address, input range, baud
rate, data format, checksum status
and/or integration time for the
specified analog input module

5-4

$AA2 Configuration

Status

Return the configuration
parameters for the specified
analog input module

5-10

$AAF

Read Version

Return the firmware version code
from the specified analog input
module

5-12

$AAM Read

Module

Name

Return the module name from the
specified analog input module

5-13

#AAN Read

Analog

Input

from Channel N

Return the input value from
channels number N of the
specified analog input module

5-16

$AA5VV Enable/disable

Channels for
Multiplexing

Enables/disables multiplexing
simultaneously for seperate
channels of the specified input
module

5-17

$AA6 Read

Channel

Status

Ask the specified input module to
return the status of all eight
channels

5-18

$AA0

Span Calibration

Calibrate the analog input module
to correct for gain errors

5-19

$AA1

Offset Calibration

Calibrate the analog input module
to correct for offset errors

5-20

$AA3

CJC Status

Returns the value of the CJC
sensor for a specified analog input
module

5-25

$AA9SNNNN CJC

Offset

Calibration

Calibrates the CJC sensor for
offset errors

5-26

@AACCCSDMTTTT

Set Memory
Configuration

Set the channel storage status,
standalone mode, data logger
mode, storage type and sampling
interval for the specified analog
input data logger.

5-37

@AAD Read

Memory

Configuration

Return the configuration
parameters for the specified
analog input data logger.

5-39

@AASO Set

Memory

Operation Mode

Start/stop the recording function of
the memory module.

5-40