Chapter – Advantech Data Acquisition Modules ADAM 4000 User Manual
Page 46

Chapter
3
Chapter 3 I/O Modules 3-19
Technical specification of ADAM-4015
Channel Number 6
differential
Support Protocol
ADAM ASCII and MODBUS/RTU
Input Type
Pt100, Pt1000, BALCO500, Ni
Input Connections
2 or 3 wires
Wire Burnout Detection
Yes
Input Type and
Temperature Range
Pt100: -50 to 150° C
0 to 100° C
0 to 200° C
0 to 400° C
-200 to 200° C
Pt1000: -40 to 160° C
Balco500: -30 to 120° C
Ni 50 RTD: -80 to 100° C
Ni 508 RTD: 0 to 100° C
Isolation Voltage 3000
V
DC
Sampling Rate
10 sample/second (total)
Input Impedance 10
MΩ
Resolution
16-bit
Accuracy
±0.1% or better
CMR@50/60Hz
120 dB
NMR@50/60Hz
100 dB
Span Drift
±
25 ppm/℃
Zero Drift
±
3 μV/℃
Watchdog Timer
System (1.6 second) and Communication
Power Input
+10~+30 V
DC
(non-regulated)
Power Consumption 1.2
W
@
24V
DC
Table 3-1 Technical specification of ADAM-4015