beautypg.com

Advantech Data Acquisition Modules ADAM 4000 User Manual

Page 122

background image

Chapter

4


Chapter 4 Command Set 4-19

ADAM-4018+ Command Table (Continued)

Command Syntax

Command Name

Command Description

Page No.

$AA1Ci Offset

Calibration

Offset error calibrate of assignment
channel, User have to input the external
standard source for calibrating process

5-28

$AA7CiRrr Input

Range Setting

Input range setting individually

5-29

$AA8Ci

Read Input Range

Get the input range of the assignment
channel

5-30

$AAXnnnn Set

Communication

WDT

Set communication WDT cycle time from
0000 ~ 9999 (unit: 0.1 second. if value is
0000, the communication WDT function
will be disable)

5-31

$AAY Get

Communication

WDT Setting

Read the cycle time setting of
communication WDT

5-32


ADAM-4018+
Input range and external calibrating input source for each input type

Range

bcode(Hex)

Input Range

Max. Signal

Min Signal

Displayed

Resolution

06 +/-20

mA

+20.000

-20.000

1uA

07 4~20

mA

+20.000

+4.000

1uA

14 Type

J

Thermocouple

15 Type

K

Thermocouple

16 Type

T

Thermocouple

17 Type

E

Thermocouple

18 Type

R

Thermocouple

19 Type

S

Thermocouple

20 Type

B

Thermocouple