beautypg.com

Advantech Data Acquisition Modules ADAM 4000 User Manual

Page 173

background image

Chapter

5


5-27

ADAM 4000 Series User’s Manual

4015, 4015T, 4017+, 4018+, 4019+

$AA1Ci

Name Single Channel Offset Calibration command

Description The command calibrates a specified channel to correct for

offset errors.

Syntax

$AA1Ci(cr)

$

is a delimiter character.

AA

(range 00-FF) represents the 2-character hexadecimal

address of the analog input module which is to be
calibrated.

1

is the Single Channel Offset Calibration command.

Ci

represents the specified input channel you want to

calibrate.

(cr)

is the terminating character, carriage return (0Dh).

Response

!AA(cr)

if the command was valid.

?AA(cr)

if an invalid operation was entered.

There is no response if the module detects a syntax error or
communication error or if the specified address does not
exist.

!

delimiter character indicates a valid command was

received.

?

delimiter character indicates the command was invalid.

AA

(range 00-FF) represents the 2-character hexadecimal

address of the analog input module.

(cr)

represents terminating character, carriage return (0Dh).

Example command: $021C5(cr)

response: !02(cr)

The command calibrates channel 5 of the analog input
module at address 02 for correcting offset errors.