Analog Output Module Command Set
6-20 ADAM 4000 Series User’s Manual
ADAM-4024 Command Review: (Continued)
Command Set Function
Response
Exam ple
#AAECn(data) Set data As CHn Emergency Stop Data
!AAECn (data)
#02EC2 +07.456
#02EC1 -03.454
#02EC0 +11.234
#**
Synchronous Sample IDI
No Response
#**
$AA0Cn
Set Current Trim Data As CHn 4m A
Calibration Parameter/EEPROM
!AA
$020C2
$AA1Cn
Set Current Trim Data As CHn 20m A
Calibration Parameter/EPROM
!AA
$021C2
$AA2
Read Back Module Status
!AATTCCFF
$022
$AA3Cn(m)
Set Trim Data For CHn
m :0 ~ 127
And If Negative Then Add 0x80 (m =xx )
Ex.m=89 → -9 m=09 → +9
!AA
$02308
$AA4
Read Back The IDI Input By Synchronous
Command (#**)
!AAx
$024
$AA5
Checks the Reset Status of the analog
output module to see whether it has been
reset since the last Reset Status
command was issued.
!AAS
$025
$AA6Cn
Read Back CHn Last Output Value
!AA(data)
$026C2
$AA7CnRxx
Set CHn Output Type
AA:
Current Module Address
Cn:
Channel
C: Prefix Command String
n = 0,1,2,3
Rxx:
Output Type (Range)
R: Prefix Command String
xx = 32 -10 V ~ +10 V
xx = 30 0 ~ 20 mA
xx = 31 4 ~ 20 mA
!AA
$027C2R32
4024