Advantech Data Acquisition Modules ADAM 4000 User Manual
Page 310

Chapter
7
7-75 ADAM 4000 Series User’s Manual
@AASA(data)
Name
Set Hi-alarm Count Value of Counter 0 command
Description
Set the high-alarm count value for counter 0 of the
specified counter module.
Syntax
@AASA(data)(cr)
@
is a delimiter character.
AA
(range 00-FF) represents the 2-character hexadecimal
address of the module.
SA
is the Set High-alarm Count Value of Counter 0
command.
(data)
is the high-alarm count value which must consist of
eight hexadecimal digits. This value should be higher than
the low-alarm count value.
(cr)
is the terminating character, carriage return (0Dh).
Response
!AA(cr)
if the command is valid.
There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.
!
is a delimiter character which indicates a valid command.
AA
(range 00-FF) represents the 2-character hexadecimal
address of the module.
(cr)
is the terminating character, carriage return (0Dh).
Example command:
@12SAF0000000(cr)
response: !12(cr)
The command sets the low-alarm count number
F0000000(hex) for channel 0 of the counter modules at
address 12. The addressed module replies that the
command has been received.