Advantech Data Acquisition Modules ADAM 4000 User Manual
Page 153

Chapter
5
5-7
ADAM 4000 Series User’s Manual
4011, 4011D, 4012, 4013, 4015, 4015T, 4016,
4017, 4017+, 4018, 4018+, 4018M, 4019+
Input Range Code (Hex)
Input Range for 4013
20
Platinum, -100 ~ 100 ℃, a=0.00385
21
Platinum, 0 ~ 100 ℃, a=0.00385
22
Platinum, 0 ~ 200 ℃, a=0.00385
23
Platinum, 0 ~ 600 ℃, a=0.00385
24
Platinum, -100 ~ 100 ℃, a=0.003916
25
Platinum, 0 ~ 100 ℃, a=0.003916
26
Platinum, 0 ~ 200 ℃, a=0.003916
27
Platinum, 0 ~ 600 ℃, a=0.003916
28
Nickel, -80 ~ 100 ℃
29
Nickel, 0 ~ 100 ℃
ADAM-4015/4015T command codes against Input ranges table
Command Code (Hex)
Input Type
Input Range
20
Platinum 100 (IEC)
-50 ~ 150 ℃
21
Platinum 100 (IEC)
0 ~ 100 ℃
22
Platinum 100 (IEC)
0 ~ 200 ℃
23
Platinum 100 (IEC)
0 ~ 400 ℃
24
Platinum 100 (IEC)
-200 ~ 200 ℃
25
Platinum 100 (JIS)
-50 ~ 150 ℃
26
Platinum 100 (JIS)
0 ~ 100 ℃
27
Platinum 100 (JIS)
0 ~ 200 ℃
28
Platinum 100 (JIS)
0 ~ 400 ℃
29
Platinum 100 (JIS)
-200 ~ 200 ℃
2A Platinum
1000
-40 ~ 160 ℃
2B BALCO
500 -30 ~ 120 ℃
2C Ni
604
-80 ~ 100 ℃
2D Ni
604
0 ~ 100 ℃
IEC RTD 100O,
α = 0.00385
JIS RTD 100O,
α = 0.00391