5-12

ADAM 4000 Series User’s Manual

4011, 4011D, 4012, 4013, 4015, 4015T, 4016,
4017, 4017+, 4018, 4018+, 4018M, 4019+

$AAM

Name

Read Module Name command

Description

The command requests the analog input module at address
AA to return its name.

Syntax

$AAM (cr)

$

is a delimiter character.

AA

(range 00-FF) represents the 2-character hexadecimal

address of the analog input module that you want to
interrogate.

M

is the Read Module Name command.

(cr)

is the terminating character, carriage return (ODh).

Response

!AA(Module Name)(cr)

if the command is valid.

There is no response if the module detects a syntax error or
communication error, or if the specified address does not
exist.

!

is a delimiter character indicating a valid command was

received.

AA

(range 00-FF) represents the 2-character hexadecimal

address of an analog input module.

(Module Name)

is the name of the module at address AA.

(cr)