beautypg.com

Chapter, Adam-4024 command review: (continued) – Advantech Data Acquisition Modules ADAM 4000 User Manual

Page 235

background image

Chapter

6


6-21 ADAM 4000 Series User’s Manual

ADAM-4024 Command Review: (Continued)

Command Set

Function

Response

Example

$AA8Cn

Read Back CHn Output Range

!AACnxx

$027C2

$AAACnZ

Enable/Disable (Z=1/0) CHn EMS Flag

!AA

$02AC21
$02AC20

$AABCn Read

CHn

EMS

Flag

!AACn1
!AACn0

$02BC2

$AADCn

Read Back CHn StartUp Data

!AA(data)

$02DC2

$AAECn

Read Back CHn Emergency Stop Data

!AA(data)

$02EC2

$AAF

Read Firmware Version

!AAAx.xx

$02F

$AAG

Reset Current Trim Data Variable To 0

!AA

$02G

$AAH

Read Current Trim Data Variable

!AAxx (xx=m)

$02H

$AAI Read

IDI

!AAx

$02I

$AAM Read

Module

Name

!AA4024 $02M

$AANCn

Read Back CHn 4mA Calibration
Parameter

!AAxx $02NC2

$AAOCn

Read Back CHn 20mA Calibration
Parameter

!AAxx

$02OC2

$AAPCn

Clear CHn 4mA Calibration Parameter /
EEPROM

!AA

$02PC2

$AAQCn

Clear CHn 20mA Calibration Parameter /
EEPROM

!AA

$02QC2

$AAXnnnn

This command set the communication
watchdog timer (WDT) cycle time.

AA:

(range 00-FF) 2-character

hexadecimal address of the analog input
module which is to be read.

X:

the setting WDT command.

Nnnn:

(range 0000~9999) the specified

value of communication cycle you want to
set. (Unit: 0.1 second)

!AA

$02X1234

$AAY

Read Communication Watchdog Timer
Cycle Setting.

AA:

(range 00-FF) 2-character

hexadecimal address of the analog input
module which is to be read.

Y:

the reading WDT cycle command.

!AA

$02Y

4024