Chapter, Adam-4024 command review: (continued) – Advantech Data Acquisition Modules ADAM 4000 User Manual
Page 235

Chapter
6
6-21 ADAM 4000 Series User’s Manual
ADAM-4024 Command Review: (Continued)
Command Set
Function
Response
Example
$AA8Cn
Read Back CHn Output Range
!AACnxx
$027C2
$AAACnZ
Enable/Disable (Z=1/0) CHn EMS Flag
!AA
$02AC21
$02AC20
$AABCn Read
CHn
EMS
Flag
!AACn1
!AACn0
$02BC2
$AADCn
Read Back CHn StartUp Data
!AA(data)
$02DC2
$AAECn
Read Back CHn Emergency Stop Data
!AA(data)
$02EC2
$AAF
Read Firmware Version
!AAAx.xx
$02F
$AAG
Reset Current Trim Data Variable To 0
!AA
$02G
$AAH
Read Current Trim Data Variable
!AAxx (xx=m)
$02H
$AAI Read
IDI
!AAx
$02I
$AAM Read
Module
Name
!AA4024 $02M
$AANCn
Read Back CHn 4mA Calibration
Parameter
!AAxx $02NC2
$AAOCn
Read Back CHn 20mA Calibration
Parameter
!AAxx
$02OC2
$AAPCn
Clear CHn 4mA Calibration Parameter /
EEPROM
!AA
$02PC2
$AAQCn
Clear CHn 20mA Calibration Parameter /
EEPROM
!AA
$02QC2
$AAXnnnn
This command set the communication
watchdog timer (WDT) cycle time.
AA:
(range 00-FF) 2-character
hexadecimal address of the analog input
module which is to be read.
X:
the setting WDT command.
Nnnn:
(range 0000~9999) the specified
value of communication cycle you want to
set. (Unit: 0.1 second)
!AA
$02X1234
$AAY
Read Communication Watchdog Timer
Cycle Setting.
AA:
(range 00-FF) 2-character
hexadecimal address of the analog input
module which is to be read.
Y:
the reading WDT cycle command.
!AA
$02Y
4024