Digital I/O and Relay Output

Counter/Frequency Command Set


7-24 ADAM 4000 Series User’s Manual

$AAP

Name

Read the Low Power Status of Module command

Description

The command requests the module at address AA to return
the low power status of module

Syntax

$AAP(cr)

$

is a delimiter character.

AA

(range 00-FF) represents the 2-character hexadecimal

address that you will access to.

P

is the Read the Low Power Status of Module command.

(cr)

is the terminating character, carriage return (ODh).

Response

!AAS(cr)

if the command was valid.

?AA(cr)

if an invalid command has been issued.

There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.

!

is a delimiter character which indicates a valid command

?

is a

delimiter character which indicates an invalid command

AA

(range 00-FF) represents the calibrated 2-character

hexadecimal address of the module.

S

represents the Status bit from the low power status. When

the logic equals to 1, it represents low power. When it equals
to zero, it means normal.

(cr)

is the terminating character, carriage return (0Dh).