1 analog input common command set – Advantech Data Acquisition Modules ADAM 4000 User Manual
Page 148

5-2
ADAM 4000 Series User’s Manual
5.1 Analog Input Common Command Set
Command
Syntax
Description I/O
Module
%AANNTTCCF
F
Sets the address, input range,
baud rate, data format,
checksum status, and/or
integration time for a specified
analog input module
4011, 4011D, 4012, 4013, 4015,
4015T, 4016, 4017, 4017+, 4018,
4018+, 4018M, 4019+
$AA2 Returns
the
configuration
parameters for the specified
analog input module
4011, 4011D, 4012, 4013, 4015,
4015T, 4016, 4017, 4017+, 4018,
4018+, 4018M, 4019+
$AAF
Returns the firmware version
code from the specified analog
input module
4011, 4011D, 4012, 4013, 4015,
4015T, 4016, 4017, 4017+, 4018,
4018+, 4018M, 4019+
$AAM
Returns the module name from
the specified analog input
module
4011, 4011D, 4012, 4013, 4015,
4015T, 4016, 4017, 4017+, 4018,
4018+, 4018M, 4019+
#AA
Returns the input value from a
specified analog input moudule
in the currently configured data
format
4011, 4011D, 4012, 4013, 4015,
4015T, 4016, 4017, 4017+, 4018,
4018+, 4019+
#AAN
Returns the input value from
channel number n of the
specified analog input module
4015, 4015T, 4017, 4017+, 4018,
4018+, 4018M, 4019+
#AA5VV Enables/disables
multiplexing
simultaneously for separate
channels of the specified input
module
4015, 4015T, 4017, 4017+, 4018,
4018+, 4018M, 4019+
$AA6
Ask the specified input module
to return the status of all eight
channels
4015, 4015T, 4017, 4017+, 4018+,
4018, 4018M, 4019+
$AA0
Calibrate the analog input
module to correct for gain errors
4011, 4011D, 4012, 4013, 4016,
4017, 4018, 4018M
$AA1
Calibrate the analog input
module to correct for offset
errors.
4011, 4011D, 4012, 4013, 4016,
4017, 4018, 4018M
#**
Orders all analog input modules
to sample their input values and
store them in special registers
4011, 4011D, 4012, 4013, 4015,
4015T, 4016
(Continued on following page)