Chapter 4 Command Set 4-25



ADAM-4024 Command Table

Command Syntax

Command Name

Command Description

Page
No.

%AANNTTCCFF

Configuration

Set the address, output range,
baud rate, data format, slew rate
and/or checksum status

6-19

#AACn(data)

Analog Data Out

Directs output data to a specified
module

6-20

#AASCn(data)

Set Startup Data Set data As CHn StartUp Data

6-20

#AAECn(data)

Set Emergency
Stop

Set data As CHn Emergency
Stop Data

6-20

#**

N/A

Synchrous Sample IDI

6-20

$AA0Cn

4 mA Calibration

Tells the module to store
parameters for 4 mA Calibration

6-20

$AA1Cn

20 mA Calibration

Tells the module to store
parameters for 20 mA Calibration

6-20

$AA2 Configuration

Status

Read back Module status

6-20

$AA3Cn(number of
counts)

Trim Calibration

Trims specified module a number
of units up/down

6-20

$AA4 Start-up

output

current/voltage
configuration

Stores a default output value in a
specified module. The output
value will take effect upon startup.

6-20

$AA5

Reset Status

Read Back Reset Times After Last
$AA5 CMD And Clear This ounter

6-20

$AA6Cn Last

Value

Readback

Returns either last value sent to
specified module by #AA
command, or start-up output
current/voltage

6-20

$AA7CnRxx

Set Output Type

Set CHn Output Type

6-20

$AA8Cn

Current Readback Returns measured value of the

current/voltage flowing through
current loop

6-21

$AAF Read

Firmware

Version

Return the firmware version code
from the specified analog output
module

6-21

$AAM Read

Module

Name

Return the module name from the
specified analog output module

6-21

(Continued on following page)