Advantech Data Acquisition Modules ADAM 4000 User Manual

Page 198

background image




5-52

ADAM 4000 Series User’s Manual

4011, 4011D, 4012, 4016

@AAEAT

Name Enable

Alarm

command

Description

The addressed analog input module is instructed to enable
its alarm in either Latching or Momentary mode.

Syntax

@AAEAT(cr)

@

is a delimiter character.

AA

(range 00-FF) represents the 2-character hexadecimal

address of an analog input module.

EA

is the Enable Alarm command.

T

indicates alarm type and can have the value M =

Momentary alarm state, or L = Latching alarm state.

(cr)

represents terminating character, carriage return (0Dh).

Response

!AA(cr)

if the command was valid.

There is no response if the module detects a syntax error or
communication error or if the specified address does not
exist.

!

delimiter character indicates a valid command was

received.

AA

represents the 2-character hexadecimal address of the

responding analog input module.

(cr)

represents terminating character,

carriage return (0Dh).

Example

command:

@03EAL(cr)

response:

!03(cr)

The analog input module at address 03h is instructed to
enable its alarm in Latching mode.

The module confirms that the command has been received.

NOTICE: An analog input module requires a maximum of 2 seconds

after

it received an Enable Alarm command to let the settings take
effect . During this interval, the module can not be addressed to
perform any other actions.