Chapter

5


5-33

ADAM 4000 Series User’s Manual

4015, 4015T

$AAS1

Name Reload Default Calibrating Parameter command

Description Reload factory default calibrating parameter to overwrite

current calibrating parameter.

Syntax

$AAS1(cr)

$

is a delimiter character.

AA

(range 00-FF) represents the 2-character hexadecimal

address of the analog input module which is to be reloaded.

S1

is the Reload Calibrating Parameter command.

(cr)

is the terminating character, carriage return (0Dh).

Response

!AA(cr)

if the command was valid.

?AA(cr)

if an invalid operation was entered.

There is no response if the module detects a syntax error or
communication error or if the specified address does not
exist.

!

delimiter character indicates a valid command was

received.

?

delimiter character indicates the command was invalid.

AA

(range 00-FF) represents the 2-character hexadecimal

address of the analog input module.

(cr)