Advantech Data Acquisition Modules ADAM 4000 User Manual
Page 302

Chapter
7
7-67 ADAM 4000 Series User’s Manual
@AARP
@AARA
Name
Read Alarm Limit Value of Counter 0 or 1 command
Description
Read the alarm limit value of counter 0 or 1 of the specified
counter module at address AA.
Syntax
@AARP(data)(cr)
@AARA(data)(cr)
@
is a delimiter character.
AA
(range 00-FF) represents the 2-character hexadecimal
address of the module.
RP
represents the Read Alarm Limit Value for counter 0
command.
RA
represents the Read Alarm Limit Value for counter 1
command.
(cr)
is the terminating character, carriage return (0Dh).
Response
!AA(data)(cr)
if the command is valid.
There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.
!
is a delimiter character which indicates a valid command.
AA
(range 00-FF) represents the 2-character hexadecimal
address of the module.
(data)
is the alarm limit value which must consist of eight
hexadecimal digits.
(cr)
is the terminating character, carriage return (0Dh).
Example
command: @12RP(cr)
response:
!120000FFFF(cr)
The command instructs the module at address 12h to return
the alarm limit value of counter 0. The module replies
that the alarm limit value of counter 0 is 0000FFFF.