Advantech Data Acquisition Modules ADAM 4000 User Manual
Page 350

Technical Specifications
A-22 ADAM 4000 Series User’s Manual
A.9 ADAM-4019+ 8-Channels Universal Analog Input
Module
Table A-13 ADAM-4019+ Specifications
AI channel number 8
Input type
V, mV, mA and T/C
Input range
V: ±1 V , ±2.5 V, ±5 V , ±10 V
mV: ±100 mV , ±500 mV
mA: ±20 mA (with120
Ω
resister)
4~20 mA(with 120
Ω
resister)
Thermocouple:
J 0 to 760 ℃
K 0 to 1370 ℃
T -100 to 400 ℃
E 0 to 1400 ℃
R 500 to 1750 ℃
S 500 to 1750 ℃
B 500 to 1800 ℃
Isolation voltage
3000 V
DC
Resolution
16-bit
Sampling rate
10 samples/sec (total)
Input impedance
20 MΩ
Accuracy
±
0.1% or better
Zero drift
±6 μV/℃
CMR @ 50/60 Hz
120 dB
NMR @ 50/60 Hz
100 dB
Span drift
±25 ppm/℃
Support protocol
ADAM ASCII and MODBUS/RTU
Watchdog timer
System (1.6 second) and communication
Power requirements +10 to +30 V
DC
(non-regulated)
Power consumption 1.0 W @ 24 V
DC
Burn-out detection
+4~20mA and all Thermocouple input