Digital I/O and Relay Output

Counter/Frequency Command Set


7-48 ADAM 4000 Series User’s Manual

$AA7N

Name

Read/Clear Overflow Flag command

Description

The command requests the module to return the status of
the overflow flag for either counter 0 or counter 1. Then
clear the flag afterwards.

Syntax

$AA7N(cr)

$

is a delimiter character.

AA

(range 00-FF) represents the 2-character hexadecimal

address that you will access to.

7

is the Read/Clear Overflow Flag command.

N

determines the channel whose overflow flag status

should be read and cleared. When N = 0, it represents
counter 0. On the other hand, N = 1 represents counter 1

(cr)

is the terminating character, carriage return (0Dh).

Response

!AAV(cr)

if the command is valid.

?AA(cr)

if an invalid operation was entered.

There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.

!

is a delimiter character which indicates a valid command.

?

is a delimiter character which indicates an invalid

command .

AA

(range 00-FF) represents the 2-character hexadecimal

address of the module.

V

represents the status of the Nth channel's overflow flag.

V = 1 means that the overflow flag has been set because the
counting has exceeded the maximum count.
V = 0 means that the overflow flag has not been set.

(cr)

is the terminating character, carriage return (0Dh).

Example command:

$1371(cr)

response: !131(cr)
The command requests the counter/frequency module at
address 13 to return the status of the overflow flag for
counter 1 and to reset it. The module replies with the
overflow flag for counter 1indicating overflow. Then it is
being reset.

4080, 4080D