ADAM 4000 Series User’s Manual

4011, 4011D, 4012, 4013, 4015, 4015T, 4016,
4017, 4017+, 4018, 4018+, 4018M, 4019+

$AA2

Example command:

$452(cr)

response:

!45050600(cr)

The command asks the analog input module at address 45h
to send its configuration data.

The analog input module at address 45h responds with an
input range of 2.5 volts, a baud rate of 9600 bps,

an

integration time of 50 ms (60 Hz), engineering units are the
currently configured data format, and no checksum
function or checksum generation.